Plan Review Notes
Plan Review Notes For Permit 07020305
Permit Number 07020305
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-03 14:04:19** UNSAT 2RDREVIEW **
  
  
 ** PLEASE SEE THERE ARE MANY COMMENTS FROM THE PREVIOUS
 REVIEWWHICH ARE STILL IN NEED OF ADDRESSING.
 **PLEASE ALSO SEE SEVERAL NEW COMMENTS BASED ON NEW
 PLANS WHICH ARE FROM CHANGES AND INFORMATION WHICH IS
 NOW BEING SUBMITTED FOR THE FIRST TIME FOR REVIEW.
  
 ***IMPORANT***
 PLEASE ALSO KNOW DUE TO THE PLANS NOT BEING COMPLETE AT
 THIS TIME AND THE FOLLOWING COMMENTS FOR PLANS
 SUBMITTED, THERE MAY BE COMMENTS ON NEXT REVIEW WHICH
 ARE NOT ON THIS REVIEW.
 **** DUE TO THE EXTENT OF THE ELECTRICAL COMMENTS, ONE
 SET OF THE ELECTRICAL PLANS ARE BEING RETAINED. PLEASE
 SEE COMMENTS WITH RESPECT TO FLORIDA STATUTES FOR
 REPEAT COMMENTS.
  
  
  
 1) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS WHICH DO
 NOT CONTAIN THE CORRECT CODES. PLEASE SEETHE CODES
 LISTED BELOW WHICH WERE PREVIOUSLY NOTED.
 PLEASE BE SURE THE PLANS STATE ALL OF THE CURRENT
 ADOPTED CODES ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
  
  
 2) NOTE:PLEASE SEE THAT COMPLIANCE WITH CHAPTER 13
 HAS NOT BEEN INDICATED. PLEASE SEE THE LIGHTING
 CONTROLS NEED TO BE SHOWN IN DETAIL FOR TYPES, TIMES ON
 OVER RIDES ETC. IF A LC SYSTEM IS TO BE INSTALLED,
 PLEASE INDICATE SCHEDULING AND OVER RIDES.
 PLEASE SEE THAT EACH DEVICE NEEDS TO BE SHOWN. RESPONSE
 WAS THAT *DUAL SWITCHING HAD BEEN ADDED*IT IS UNCLEAR
 WHERE THIS IS FROM? IS THIS MEANT TO RESPOND TO *TANDEM
 WIRING* AS STATED IN 13-415.1.ABC.3?
 PLEASE COMPLETE FIXTURE LEGEND. PLEASE SEE LEGEND
 MENTIONS A *STANDARD FLUORESCENT FIXTURE* HOWEVER DUE
 TO THE FACT THERE IS NO STANDARD FIXTURE ON THE MARKET,
 ONE IS TO BE SPECIFIED.
 PLEASE SEE ENERGY CALCULATIONS ARE TO BE UNDER THE 2006
 REVISIONS TO THE 2004 FBC. PLEASE VERIFY VERSION,
 PLEASE ALSO VERIFY METHOD FOR WHOLE BUILDING WHEN THIS
 IS A TENANT SPACE WHICH IS PART OF A LARGER *BUILDING*
 BY DEFINITION.
 PLEASE SEE THE ENERGY CALCULATIONS FOR SOME KW RATINGS
 DO NOT MATCH WITH ELECTRICAL PLANS FOR THE SAME LOADS
 ON APPLIANCES. PLEASE SEE THE CALCULATIONS DO NOT
 CORRELATE AS SOME SHEETS INDICATE ONE LOAD FOR WATER
 HEATER AND ANOTHER SHEET INDICATES A LARGER LOAD?
 PLEASE ADJUST AND CORRELATE ALL.
 PLEASE SEE THE 2004 FBC CHAPTER 13 FOR LIGHTING
 CONTROLS PER 13-415.1.ABC.1.1, .1.2 AND .1.3. PLEASE
 ALSO SUBMIT ENERGY CALCULATIONS AND PERFORMANCE
 CALCULATIONS PER 13-415.1AB.1.1, 13415.2.
  
 3) NOTE:PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL(S).
 PLEASE SEE THIS IS THE FIRST REVIEW WHERE PANELS ARE
 BEING SUBMITTED FOR REVIEW.
 A) PLEASE SEE THE RISER IS NOT COMPLETE AS IS DOES NOT
 SHOW HOW PANEL *B* IS BEING FED.
 B) PLEASE SEE RISER NOW SHOWS NEW PANELS, DISCONNECTS
 AND METERS, YET THE RISER SHOWS THE CONDUCTORS AS
 EXISTING?
 C) PLEASE SEE THE LOAD AND THE SIZE OF THE PANEL *A*
 EXCEEDS THE RATING OF THE PROPOSED 100AMP DISCONNECT AS
 SHOWN ALONG WITH CONDUCTORS ETC.
 PLEASE SEE THE LOAD IS SHOWN AT 134+ AMPS, ON A 150A
 MCB PANEL. (FED FROM100AMP DISCONNECT?)
 D) PLEASE SEE PANEL *B* DOES NOT SHOW WHERE IT IS BEING
 FED FROM? NO OCP, CONDUCTORS ETC.?
 PLEASE KNOW, AT THIS TIME RISER IS NOT COMPLETE FOR
 REVIEW.
 PLEASE SUBMIT A PANEL SCHEDULE WHICH WILL CORRELATE
 WITH ALL OF THE CIRCUITING AS SHOWN ON PLANS. PLEASE BE
 SURE ALL OF THE CIRCUITS NEW AND EXISTING ARE SHOWN,
 THE SIZE OF THE PANEL, THE OVER CURRENT PROTECTION
 DEVICES AND THE CONDUCTORS SIZES. 215.5, 408.4, 310.16,
 240.4 ETC
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE BE SURE BOTH SETS OF PLANS ARE COMPLETE
 WITH ALL SHEETS INSERTED AND MADE INTO SETS. MANY OF
 THE SHEETS SUBMITTED ARE LOOSE AND NOT IN SETS OR
 ATTACHED IN ANY FASHION.
  
 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 ALL EXISTING LOADS AND NEW LOADS BEING ADDED TO THE
 PANEL.
 AS PREVIOUSLY STATED, INCLUDE ALL NEW LOADS ON THE
 EXISTING SERVICE, INCLUDE LOAD OF THE EXISTING SERVICE
 WHERE THE PROPOSED NEW TENANT SERVICE IS BEING SHOWN.
 PLEASE SEE THE LOAD CALCULATIONS ARE NOT COMPLETE
 AND/OR DO NOT SHOW HOW THE FINAL LOADS FOR TRACK
 LIGHTING DERIVED.
 SHOWS THE 150VA PER 2FT, HOWEVER THE TOTAL FT AND LOAD
 FOR THIS COULD NOT BE LOCATED IN ANY BREAKDOWN.
 PLEASE SEE AS PANEL *B* DOES NOT INDICATE HOW THIS IS
 BEING FED, IT IS UNCLEAR WHERETHE LOADS ARE BEING
 ADDED. ARE THESE LOADS ON PANEL *A*?
 AS THERE ARE SEVERAL ITEMS WHICH ARE NOT COMPLETE ARE
 STATED IN NOTE #3 ABOVE, SOME COMMENTS CAN NOT BE MADE
 OR ITEMS REVIEWED.
 PLEASE BE SURE TO SHOW THE SIZE OF THE MAIN/OVER
 CURRENT PROTECTION, SIZE OF SERVICE PROVIDED. PLEASE
 SEE 220.12,220.14, 220.42, 220.44, ETC. PLEASE SEE
 215.3, 230.42 AND SHOW ALL CONTINUOUS LOADS AT 125%.
  
 6) NOTE:THIS NOT WILL REMAIN AS NOTED ABOVE. PLEASE
 SEE 220.43B FOR MINIMUM CALCULATIONS TO BE SHOWN FOR
 TRACK LIGHTING.
  
 7) NOTE:THIS NOT REMAINS AS THE CORRECT LOADS FOR
 SERVICE ARE NOT COMPLETE FOR CODE COMPLIANCE. WHERE ARE
 LOADS IN LOAD CALCULATIONS AS REQUIRED PER SECTIONS
 BELOW?
 PLEASE SEE MISSING SHOW WINDOW RECEPTACLES WHICH WILL
 BE REQUIRED PER 210.62 AND LOADS TO BE SHOWN PER
 210.43A.
  
 8) NOTE:PLEASE SEE MISSING LICENSE INFORMATION FOR
 *STORETECH* WHICH IS BEING LISTED ON TITLE BLOCKS AS
 DESIGNERS?
 PLEASE SEE FS 471.023, 481.219.
 FAC 61G1-16.004, 61G15-23.002
 THIS IS A NEW COMMENT HOWEVER MUST BE ADDRESSED.
  
 9) NOTE:THIS COMMENT IS TO REMAIN. PLEASE SEE THAT NO
 RESPONSE WAS MADE IN THE RESPONSE LETTER FOR THIS?
 PLEASE SEE THAT THE SIGNATURE ON THE RESPONSE LETTER IS
 DIFFERENT THAN THAT OF THE SIGNATURE ON PLANS.
 PLEASE ALSO SEE THIS LETTER DOES *NOT* CONTAIN AN
 ORIGINAL SIGNATURE. THE LETTER IN FACT CONTAINS A
 RAISED SEAL OVER A *PHOTO-COPIED* SIGNATURE.
 NOW THAT TWO SIGNATURES HAVE BEEN PRESENTED, THIS
 OFFICE HAS NO WAY TO VERIFY WHICH THE LEGAL SIGNATURE
 OF THE DESIGNER OR RECORD IS. PLEASE SEND A COPY OF THE
 DRIVER'S LICENSE ALONG WITH THE REQUESTED NOTARIZED
 LETTER. THIS DL # AND PERSONNEL ADDRESS INFORMATION MAY
 BE CROSSED OUT. PLEASE BE SURE ALL RAISED SEALS ARE
 CLEAR AND VISIBLE WITH ALL INFORMATION ON SAID SEAL.
 PLEASE SEE MANY OF THEM ARE VERY FAINT AND NOT EASILY
 READ. PLEASE SEE FS 481.221,471.025
 PLEASE ALSO SEE PLANS APPEAR TO BE SIGNED WITH
 INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 DESIGNER OF RECORD, PLEASE PROVIDE A SIGNED, DATED,
 SEALED AND NOTARIZED LETTER FOR SIGNATURE VERIFICATION.
 THIS WILL BE PLACED IN SIGNATURE FILE FOR FUTURE
 REFERENCES.
 ANY LETTERS WHICH ARE NOTARIZED MUST CONTAIN THE
 STATEMENTS AS REQUIRED UNDER FS 117.05 FOR NOTARIES.
 * ONE SET OF PLANS AND LETTERS ARE BEING RETAINED BY
 THIS OFFICE.
  
 10) NOTE: PLEASE SEE VALUE SHALL BE ADJUSTED AS STATED
 FOR SCOPE PER FBC 108.3. NO RESPONSE WAS MADE TO THIS
 AND THE APPLIED VALUE REMAINS THE SAME. THE VALUE SHALL
 INCLUDE ALL LABOR AND MATERIALS AND EQUIPMENT, EVEN IF
 ANY OF THIS IS OWNER SUPPLIED.
  
 11) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) ATTACHED
 WITH RESPECT TO DESIGN PROFESSIONALS AND REPEAT
 COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  