| Notes |
| Date |
Text |
| 2007-02-26 07:28:03 | DENIED; | | | 1. FBC-2004 EXISTING BUILDING CODE CHAPTER 8; | | | A) SECTION 806 REFURES TO CHAPTER 11 OF THE | | | BUILDING CODE. SEE SECTION 11-45.22.2(1) DOORS CAN NOT | | | SWING INTO THE CLEAR FLOOR SPACE OF THE BATHROOM | | | FIXTURES. BATHROOM DOORS SHOULD SWING OUT. | | | B) EX-B CODE SECTION 810 REFURES TO FBC-2004 | | | PLUMBING. SEE TABLE 403.1 (6M) A DRINKING FOUNTAIN IS | | | REQUIRED. DRINKING FOUNTAIN MUST MEET THE REQUIREMENTS | | | OF CHAPTER 11 SECTIONS 11-4.1.3(10),11-4.15.2,3,4, | | | AND 5. PLEASE SHOW DETAIL WITH ALL REQUIRED | | | MEASUREMENTS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|