| Plan Review Notes For Permit 07020305 |
| Permit Number |
07020305 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-06 15:32:50 | ----------------DENIED------------------ | | | | | | 2004 FBC CODE FAMILY W/ 2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. ENERGY CALCULATIONS SHOW ONE RTU SYSTEM, BUT PLANS | | | INDICATE TWO SPLIT SYSTEMS. PLEASE CORRECT | | | CALCULATIONS. | | | | | | 2. M-1 IS SHOWN AS A "DUCT PLAN" BUT THERE IS NO DUCT | | | ON PLAN. PLEASE SHOW COMPLETE SCOPE OF WORK, SHOWING | | | LOCATIONS AND SIZES OF EXISTING DUCTS TO REMAIN AS WELL | | | AS NEW DUCTS. SHOW WHICH GRILLS ARE TO BE NEW AND WHICH | | | ARE TO REMAIN. SHOW LOCATION OF EXISTING A/C EQUIPMENT. | | | FBC 106.1.1 | | | | | | 3. PG T-1 STATES THAT THERE IS NO MECHANICAL OR | | | PLUMBING WORK TO BE DONE, BUT THERE IS A MECHANICAL | | | SCOPE OF WORKK AS INDICATED ON M-1. PLEASE CORRECT. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|