Plan Review Notes
Plan Review Notes For Permit 07020305
Permit Number 07020305
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-06 15:32:50----------------DENIED------------------
  
 2004 FBC CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ENERGY CALCULATIONS SHOW ONE RTU SYSTEM, BUT PLANS
 INDICATE TWO SPLIT SYSTEMS. PLEASE CORRECT
 CALCULATIONS.
  
 2. M-1 IS SHOWN AS A "DUCT PLAN" BUT THERE IS NO DUCT
 ON PLAN. PLEASE SHOW COMPLETE SCOPE OF WORK, SHOWING
 LOCATIONS AND SIZES OF EXISTING DUCTS TO REMAIN AS WELL
 AS NEW DUCTS. SHOW WHICH GRILLS ARE TO BE NEW AND WHICH
 ARE TO REMAIN. SHOW LOCATION OF EXISTING A/C EQUIPMENT.
 FBC 106.1.1
  
 3. PG T-1 STATES THAT THERE IS NO MECHANICAL OR
 PLUMBING WORK TO BE DONE, BUT THERE IS A MECHANICAL
 SCOPE OF WORKK AS INDICATED ON M-1. PLEASE CORRECT.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]