Plan Review Notes
Plan Review Notes For Permit 07020305
Permit Number 07020305
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-02-26 12:43:11*****DENIED*****
  
  
 1.THE SUITE NUMBER SHALL BE INCLUDED WITH THE ADDRESS
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED.
  
 3.INDICATE WHETHER THE BUILDING IS SPRINKLERED AND/OR
 HAS A FIRE ALARM SYSTEM.
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.SPECIFY INTERIOR FINISH MATERIAL CLASSIFICATION FOR
 WALLS AND CEILINGS.
  
 6.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).THE LOCATION OF
 THE 2A-10BC RATED FIRE EXTINGUISHERS MAY BE NOTED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW