Plan Review Notes
Plan Review Notes For Permit 07020305
Permit Number 07020305
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-15 08:32:03**** UNSAT ****
  
 1) NOTE: PLEASE BE SURE THE PLANS STATE ALL OF THE
 CURRENT ADOPTED CODES ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (IF APPLICABLE FOR ANY FIRE ALARM SYSTEM
 OR DEVICES PRESENT).
  
 ** PLEASE SEE CODES ON PLANS WHICH REFERENCE BACK TO
 THE 1996 NFPA-70.
  
 2) NOTE: PLEASE SEE THE 2004 FBC CHAPTER 13 FOR
 LIGHTING CONTROLS PER 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE ALSO SUBMIT ENERGY CALCULATIONS AND PERFORMANCE
 CALCULATIONS PER 13-415.1AB.1.1, 13415.2.
  
 3) NOTE: PLEASE SUBMIT A PANEL SCHEDULE WHICH WILL
 CORRELATE WITH ALL OF THE CIRCUITING AS SHOWN ON PLANS.
 PLEASE BE SURE ALL OF THE CIRCUITS NEW AND EXISTING ARE
 SHOWN, THE SIZE OF THE PANEL, THE OVER CURRENT
 PROTECTION DEVICES AND THE CONDUCTORS SIZES. 215.5,
 408.4, 310.16, 240.4 ETC
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE VERIFY NEW OR EXISTING SIGN CIRCUIT PER
 600.5.
 (LOAD MIN 1200VA )
  
 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 ALL EXISTING LOADS AND NEW LOADS BEING ADDED TO THE
 PANEL. PLEASE BE SURE TO SHOW THE SIZE OF THE MAIN/OVER
 CURRENT PROTECTION, SIZE OF SERVICE PROVIDED. PLEASE
 SEE 220.12,220.14, 220.42, 220.44, ETC. PLEASE SEE
 215.3, 230.42 AND SHOW ALL CONTINUOUS LOADS AT 125%.
  
 6) NOTE: PLEASE SEE 220.43B FOR MINIMUM CALCULATIONS TO
 BE SHOWN FOR TRACK LIGHTING.
  
 7) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES
 WHICH WILL BE REQUIRED PER 210.62 AND LOADS TO BE SHOWN
 PER 210.43A.
  
 8) NOTE: PLEASE SEE MISSING DISCONNECT FOR AHU, PER
 440.11, 110.26.
  
 9) NOTE: PLEASE BE SURE ALL RAISED SEALS ARE CLEAR AND
 VISIBLE WITH ALL INFORMATION ON SAID SEAL. PLEASE SEE
 MANY OF THEM ARE VERY FAINT AND NOT EASILY READ. PLEASE
 SEE FS 481.221.
 PLEASE ALSO SEE PLANS APPEAR TO BE SIGNED WITH
 INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 DESIGNER OF RECORD, PLEASE PROVIDE A SIGNED, DATED,
 SEALED AND NOTARIZED LETTER FOR SIGNATURE VERIFICATION.
 THIS WILL BE PLACED IN SIGNATURE FILE FOR FUTURE
 REFERENCES.
  
 10) NOTE: PLEASE SEE VALUE SHALL BE ADJUSTED AS STATED
 FOR SCOPE PER FBC 108.3.
  
 11) NOTE: PLEASE KNOW IF THE BUILDING CONTAINS ANY FIRE
 ALARM SYSTEM OR DEVICES, PLEASE INDICATE THE DEVICES ON
 THE BASE PLANS.
 PLEASE SEE FBC 11-4.28.1, .2 AND .3(4).
 FBC ADMIN SECTION 106.3
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]