| Date |
Text |
| 2007-02-15 08:32:03 | **** UNSAT **** |
| | |
| | 1) NOTE: PLEASE BE SURE THE PLANS STATE ALL OF THE |
| | CURRENT ADOPTED CODES ON PLANS. |
| | PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL |
| | AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE |
| | KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. |
| | PLEASE LIST THE FOLLOWING |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (IF APPLICABLE FOR ANY FIRE ALARM SYSTEM |
| | OR DEVICES PRESENT). |
| | |
| | ** PLEASE SEE CODES ON PLANS WHICH REFERENCE BACK TO |
| | THE 1996 NFPA-70. |
| | |
| | 2) NOTE: PLEASE SEE THE 2004 FBC CHAPTER 13 FOR |
| | LIGHTING CONTROLS PER 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE ALSO SUBMIT ENERGY CALCULATIONS AND PERFORMANCE |
| | CALCULATIONS PER 13-415.1AB.1.1, 13415.2. |
| | |
| | 3) NOTE: PLEASE SUBMIT A PANEL SCHEDULE WHICH WILL |
| | CORRELATE WITH ALL OF THE CIRCUITING AS SHOWN ON PLANS. |
| | PLEASE BE SURE ALL OF THE CIRCUITS NEW AND EXISTING ARE |
| | SHOWN, THE SIZE OF THE PANEL, THE OVER CURRENT |
| | PROTECTION DEVICES AND THE CONDUCTORS SIZES. 215.5, |
| | 408.4, 310.16, 240.4 ETC |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 |
| | |
| | 4) NOTE: PLEASE VERIFY NEW OR EXISTING SIGN CIRCUIT PER |
| | 600.5. |
| | (LOAD MIN 1200VA ) |
| | |
| | 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | ALL EXISTING LOADS AND NEW LOADS BEING ADDED TO THE |
| | PANEL. PLEASE BE SURE TO SHOW THE SIZE OF THE MAIN/OVER |
| | CURRENT PROTECTION, SIZE OF SERVICE PROVIDED. PLEASE |
| | SEE 220.12,220.14, 220.42, 220.44, ETC. PLEASE SEE |
| | 215.3, 230.42 AND SHOW ALL CONTINUOUS LOADS AT 125%. |
| | |
| | 6) NOTE: PLEASE SEE 220.43B FOR MINIMUM CALCULATIONS TO |
| | BE SHOWN FOR TRACK LIGHTING. |
| | |
| | 7) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES |
| | WHICH WILL BE REQUIRED PER 210.62 AND LOADS TO BE SHOWN |
| | PER 210.43A. |
| | |
| | 8) NOTE: PLEASE SEE MISSING DISCONNECT FOR AHU, PER |
| | 440.11, 110.26. |
| | |
| | 9) NOTE: PLEASE BE SURE ALL RAISED SEALS ARE CLEAR AND |
| | VISIBLE WITH ALL INFORMATION ON SAID SEAL. PLEASE SEE |
| | MANY OF THEM ARE VERY FAINT AND NOT EASILY READ. PLEASE |
| | SEE FS 481.221. |
| | PLEASE ALSO SEE PLANS APPEAR TO BE SIGNED WITH |
| | INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| | DESIGNER OF RECORD, PLEASE PROVIDE A SIGNED, DATED, |
| | SEALED AND NOTARIZED LETTER FOR SIGNATURE VERIFICATION. |
| | THIS WILL BE PLACED IN SIGNATURE FILE FOR FUTURE |
| | REFERENCES. |
| | |
| | 10) NOTE: PLEASE SEE VALUE SHALL BE ADJUSTED AS STATED |
| | FOR SCOPE PER FBC 108.3. |
| | |
| | 11) NOTE: PLEASE KNOW IF THE BUILDING CONTAINS ANY FIRE |
| | ALARM SYSTEM OR DEVICES, PLEASE INDICATE THE DEVICES ON |
| | THE BASE PLANS. |
| | PLEASE SEE FBC 11-4.28.1, .2 AND .3(4). |
| | FBC ADMIN SECTION 106.3 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |