| 2008-08-28 09:24:23 | REVISION DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | 1. SHT 3 OF 4. A WATER HAMMER ARRESTOR IS REQUIRED ON |
| | THE WATER SUPPLY LINE TO THE ICE MAKER. SECTION 604.9 & |
| | PDI-WH 201. |
| | |
| | 2. SHT 3 OF 4. THE NEW S-4 SINK DRAIN SHALL NOT DRAIN |
| | THRU THE HORIZONTAL WET VENT FOR THE TOILET ROOM |
| | FIXTURES. ALL OTHER FIXTURES SHALL DISCHARGE DOWNSTREAM |
| | OF THE HORIZONTAL WET VENT. SECTION 909.1. SINK SHALL |
| | CONNECT DOWNSTREAM OF THE TOILET ROOM FIXTURES. |
| | |
| | 3. SHT 3 OF 4. NEW FLOOR DRAIN IS INDICATED AS A FLOOR |
| | SINK ON THE FLOOR PLAN. A FLOOR SINK IS REQUIRED FOR |
| | INDIRECT WASTE. SECTION 802.3. FLOOR SINK SHALL CONNECT |
| | TO THE VENTED LINE PER SECTION 912.2.4, NOT TO THE |
| | BRANCH/FIXTURE LINE FOR THE OTHER FLOOR DRAIN IN SPA 2. |
| | A SEPARATE VENT FOR NEW FLOOR SINK WOULD ALSO WORK. |
| | SECTION 901.2.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |