| 2008-09-16 14:23:54 | |
| | |
| | NONCOMPLIANT/ REVISION DENIED |
| | |
| | ALL COMMENTS RELATE TO SHEET #2, UNLESS OTHERWISE |
| | NOTED. SEE REVIEWED SET FOR SOME, BUT NOT ALL, EXAMPLES |
| | OF NONCOMPLIANCE. |
| | |
| | 1} THE "EM" FIXTURES MUST BE CIRCUITED PER 700.12 NEC |
| | (F)(4). THE ADDED "EM" LIGHTS AND SOME MISSED ON |
| | PREVIOUS REVIEW, EXIT AND EMERGENY, DO NOT COMPLY. |
| | |
| | 2} THERE ARE SEVERAL MOTION SENSORS THAT HAVE BEEN |
| | REMOVED AND WERE NOT INDICATED AS A REVISION (CLOUDED) |
| | ON THE PLAN. INDICATE HOW COMPLIANCE WITH |
| | 13-415.1.ABC.1.2 SPACE CONTROL, IS TO BE ACHIEVED, OR |
| | INSTALL, THE PERMITTED DETECTORS |
| | |
| | 3} THERE ARE CHANGES IN TYPE "I" AND "J" FIXTURES AND |
| | ADDITIONS OF TYPE "H", "L", "M", AND "N" FIXTURES. IT |
| | IS NOT CLEAR HOW THE MAXIMUM WATTAGES STILL COMPLY WITH |
| | 13-415.2B FBC AS STATED IN THE NOTE ON SHEET |
| | #4,THEREFORE THE FOLLOWING IS REQUIRED: |
| | |
| | THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| | A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| | SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| | DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| | METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED |
| | INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH |
| | SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR |
| | LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| | SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE |
| | DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF |
| | THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE |
| | DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE |
| | SCHEDULE AND SQUARE FOOTAGE FOR EACH ARE IN COMPLIANCE |
| | THE WITH WATTAGE ALLOWANCE*** NOTE : OFFICE AREAS ARE |
| | NOT ALLOWED 1.5 WATTS PER SQUARE FOOT. |
| | |
| | 4} ADD THE COST OF THE ADDITIONAL LABOR, MATERIAL AND |
| | EQUIPMENT ADDED IN THIS REVISION TO THE ORIGINAL VALUE |
| | ON THE APPLICATION ADJUST THE VALUE AT THE PERMIT |
| | CLERK?S DESK, AND PAY THE DIFFERENCE IN FEES PRIOR TO |
| | RESUBMITTING. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |