| Plan Review Notes For Permit 07020267 |
| Permit Number |
07020267 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-03-31 07:50:40 | DENIED; | | | 1. WATER RISER DIAGRAM; WATER HAMMER ARRESTORS ARE | | | REQUIRED FOR ALL QUICK CLOSE VALVES ONLY. ONLY THE | | | JUICE BAR SINK AND THE AUTOMATIC CLOTHES WASHER HAVE | | | QUICK CLOSING VALVES. WATER HAMMER ARRESTORS TO BE | | | INSTALLED PER MANUFATURE SPECIFICATIONS, AT THE BOTTOM | | | OF THE DROPS NOT IN CEILING. | | | 2.SANITARY RISER DIAGRAM; ADD DRINKING FOUNTAIN TO | | | RISER DIAGRAM. | | | 3. A THERMAL EXPANSION CONTROL IS REQUIRED AT WATER | | | HEATER. SHOW OR MAKE A NOTE ON PLAN. SPEC TYPE AND SIZE | | | TO BE INSTALLED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|