| Plan Review Notes For Permit 07020267 |
| Permit Number |
07020267 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-15 10:26:30 | DENIED; | | | 1. PLUMBING FIXTURE SCHEDULE, TOILETS TO BE ELONGATED | | | TYPE (NOT SURE OF MODEL NUMBER) AND SEAT TO BE OPEN | | | FRONT. SEE FBC PLUMBING SECTIONS, 420.2 AND 420.3. | | | 2. PLUMBING NOTE # 12; SEE SECTION 410.1. THE ONLY | | | EXCEPTION FOR NOT INSTALLING A DRINKING FOUNTAIN IS FOR | | | A RESTAURANT. DRINKING FOUNTAIN IS REQUIRED , SEE TABLE | | | 403.1 (2B). | | | 3. PLUMBING NOTE # 8; PVC PIPE CAN ONLY BE USED 5' INTO | | | A BUILDING 605.3. SEE TABLE 605.4 FOR TYPE OF MATERIAL | | | THAT CAN BE USED. | | | 4. PAGE 1 FLOOR PLAN NOTE #16;SHOW A DETAIL WITH ALL | | | REQUIRED MEASUREMENTS TO MEET HANDICAP REQUIREMENTS | | | PER. FBC-2004 BUILDING CHAPTER 11. SEE SECTION | | | 11-4.24.2 THRU 11-4.24.7. | | | 5. SANITARY RISER DIAGRAM; | | | A) AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO | | | BE 3" SECTION 406.3. | | | B)FLOOR DRAIN IN WORK ROOM NOT VENTED AND | | | SHOULD HAVE A TRAP PRIMER. | | | C) F/D IN WOMAN'S ROOM NOT VENTED. | | | D) F/D IN WOMAN'S SHOWER ROOM NOT VENTED. | | | E) F/D IN MEN'S ROOM MISSING. | | | F) F/D MEN'S SHOWER ROOM NOT VENTED. | | | 6. WATER RISER DIAGRAM; AUTOMATIC CLOTHES WASHER | | | REQUIRE WATER HAMMER ARRESTORS, TOBE INSTALLED PER | | | MANUFACTURE INSTALLATION INSTRUCTIONS. SEE SECTION | | | 604.9. | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 805-6695 |
|