| 2007-02-15 16:31:20 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. FBC 2004 WITH 2006 REVISIONS |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | ------------------------------------- |
| | ) NUMBER OF UNITS |
| | ) NUMBER OF FLOORS |
| | ) NUMBER OF ROOMS |
| | ) SQ. FT. FOOTPRINT |
| | ) SQ. FT. UNDER ROOF (TOTAL) |
| | ) OCCUPANT LOAD |
| | ) FLOOD ZONE |
| | ) FLOOD ELEVATION |
| | )L.O.M.R. |
| | |
| | 4)THE VALUE ON THE APPLICATION IS LOW.108.3*IF, |
| | IN THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED |
| | VALUATION OF BUILDING, ALTERATION. STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT; |
| | EXCLUDING LAND ONLY. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS |
| | SERVICES. |
| | |
| | 5)FBC 106.3.5.1.1SUBMIT A LIFE SAFETY PLAN SHOWING |
| | THE MEANS OF EGRESS AND TRAVEL DISTANCE. IS THERE A |
| | SPRINKLER SYSTEM IN THIS AREA?CLARIFY. |
| | |
| | 6)FBC 11-7.2(2) (I) A PORTION OF THE MAIN COUNTER |
| | WHICH IS A MINIMUM OF 36 INCHES IN LENGTH SHALL BE |
| | PROVIDED WITH A MAXIMUM HEIGHT OF 36 INCHES.IN NEW |
| | CONSTRUCTION, WHERE THE SELLING SPACE IS UNDER 5,000 |
| | SQUARE FEET, ONLY ONE CHECK-OUT AISLE IS REQUIRED TEO |
| | BE ACCESSIBLE. SHOW COMPLIANCE WITH ELEVATION |
| | DRAWINGS. |
| | |
| | 7)FBC.11-5.2 WHERE FOOD OR DRINKIS SERVED AT |
| | COUNTERS EXCEEDING 34 INCHES IN HEIGHT FOR CONSUMPTION |
| | BY COUSTOMERS SEATED ON STOOLS OR STANDING AT THE |
| | COUNTER, A PORTION OF THE MAIN COUNTERWHICH IS60 |
| | INCHES IN LENGTH MINIMUM SHALL BE PROVIDED IN |
| | COMPLIANCE WITH SECTION 11-4.32 OR SERVICES SHALL BE |
| | AVAILABLE AT TABLES WITHIN THE SAME AREA. |
| | |
| | 8)CLARIFY IF THE BUILDING OR NEW SPACE HAS A |
| | SPRINKLER SYSTEM, AND IF IT DOES, STATE THE TYPE OF |
| | SPRINKLER SYSTEM ON THE DRAWINGS. SEE SHEET 1. |
| | |
| | 9)SHOWER STALLS SHALL COMPPLY WITH SECTION 11-4.21 |
| | PROVIDE AN ELEVATION DRAWINGS WITH ALL THE DIMENTIONS. |
| | |
| | 10)FBC 1210.3 SHOWER COMPARTMENTS AND WALLS ABOVE |
| | BATHBUBS WITH INSTALLED SHOWER HEADS SHALL BE FINISHED |
| | WITH A SMOOTH, NONABSORBENT SURFACE TO A HEIGHT NOT |
| | LESS THAN 70 INCHES ABOVE THE DRAIN INLET. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |