| Plan Review Notes For Permit 07020266 |
| Permit Number |
07020266 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-09-08 14:26:09 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | REVISION TO MECHANICAL PLANS M-1 AND M-2. | | | *** DENIED *** | | | | | | 1) COOLING LOAD CALCULATIONS SUBMITTED FOR A/C SYSTEM | | | #1 IS CALLING FOR 40,502 TOTAL COOLING BTU'S, THE | | | MECHANICAL PLANS ARE SHOWING SYSTEM #1 AS 57,000 TOTAL | | | COOLING BTU'S. A 5 TON A/C SYSTEM IS TO LARGE PER THE | | | COOLING LOAD CAL'S, A 3.5 TON WOULD MEET THE | | | REQUIREMENTS (SEE ATTACHED ARI CERTIFICATE), PER 2004 | | | FBC/M 13-407.1.ABC.1.1. PLEASE CORRECT. | | | | | | 2) PLEASE SHOW ON THE MECHANICAL PLANS THE OUTDOOR AIR | | | CALCULATIONS, AS THE OUTDOOR AIR BEING PROVIDED APPEARS | | | NOT TO BE ENOUGH, PER 2004 FBC/M 403.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|