| Date |
Text |
| 2007-07-06 07:57:11 | 2007-07-06 07:57:11 |
| | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS STILL DO |
| | NOT CORRELATE WITH THE FIXTURE LEGEND ON PLANS. PLEASE |
| | SEE THE RESPONSE HAND WRITTEN ON NOTES SHEETS MENTIONS |
| | THE CERTAIN FIXTURES ARE EXEMPT UNDER 13-415.2.B.2, |
| | HOWEVER PLEASE SEE THIS SECTION OF THE CODE DOES NOT |
| | APPLY TO THE CALCULATIONS SUBMITTED AND THE USE AS |
| | SHOWN. PLEASE SEE ADDITIONAL ALLOWANCES ARE PERMITTED, |
| | HOWEVER THAT DOES NOT MEAN THEY ARE EXEMPT. IN EITHER |
| | CASE THE SECTION REFERENCED IS FOR SPACE BY SPACE |
| | CALCULATIONS AND PERFORMANCE MEASURES. |
| | PLEASE SEE 13-415.1.AB.1.,13-415.1.A, 13-415.2 |
| | |
| | PLEASE REVISE AND ADJUST. |
| | |
| | 2) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS DOWN |
| | THE LEFT HADN SIDE OF THE PLANS. THESE WERE REMOVED |
| | FROM PLANS BY THIS OFFICE ON THIS REVIEW AND PLACED |
| | INTO TWO PACKAGES FOR EACH. |
| | FBC106.1 |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-06 07:02:04 | 2007-07-06 07:02:04 |
| | REVIEW IN PROGRESS |
| 2007-07-05 17:51:50 | 2007-07-05 17:51:50 |
| | PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO |
| | INCOMING WAITING FOR THE COMM BOARD ONCE ELECTRICLA |
| | REVIEW IS DONE. |