| Plan Review Notes For Permit 07020266 |
| Permit Number |
07020266 |
|
| Review Stop |
MEDGAS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-05-30 16:58:01 | DENIED | | | REFERENCE: NFPA 99C 2002 | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | | | | 4. THE EXHAUST VENT FOR THE VACUUM SHALL TERMINATE | | | SEPARATELY ABOVE THE ROOF TO OPEN AIR. SECTION 713.6. | | | ****RESPONSE NOTED, BUT THE REQUIREMENT IS NOT | | | ADDRESSED. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE. | | | | | | 5. SHT 3 AIR/VACUUM INDICATES A 1/2" FILTERED WATER | | | LINE TO THE VACUUM. PLEASE CLARIFY. SECTION 106.1.1. | | | ****RESPONSE NOTED. BACKFLOW PROTECTION IS REQUIRED FOR | | | THE WATER CONNECTION PER SECTION 608. PLEASE INDICATE | | | THE METHOD OF PROTECTION. | | | | | | 6. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|