| Date |
Text |
| 2007-03-10 16:01:14 | DENIED |
| | REFERENCE: FBC-2004 W/2006 REV. |
| | FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | |
| | 1. SHT 1 ROOM FINISH SCHEDULE. TOILET ROOMS 1 & 2 WALL |
| | FINISH INDICATES GWB PAINTED. THIS DOES NOT MEET THE |
| | REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT" WALLS AS |
| | REQUIRED IN SECTION 1210.2. PLEASE INDICATE A HARD |
| | SURFACE FOR THE WALLS AS REQUIRED. |
| | |
| | 2. SHT 1 INDICATES A FLOOR DRAIN IN THE LAB. THE RISER |
| | DIAGRAM INDICATES THIS AS A FLOOR SINK. PLEASE |
| | CORRELATE RISER AND FLOOR PLAN INFORMATION. SECTION |
| | 106.1.1. IF THE FLOOR SINK IS FOR INDIRECT WASTE, THEN |
| | A FLOOR SINK IS REQUIRED. IF SO PLEASE INDICATE WHAT |
| | WILL DRAIN INTO THE FLOOR SINK. SECTION 106.1.2. |
| | |
| | 3. SHT 2 DETAILS 4 & 5. SHOW COMPLIANCE FOR THE |
| | FOLLOWING: |
| | -WATER CLOSETS: |
| | A. 11-4.16.3 HEIGHT |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | -FOR LAVS: |
| | A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | B. 11-4.19.5 FAUCETS |
| | |
| | 4. SHT 3 WASTE RISER DIAGRAM DOES NOT REFLECT THE FLOOR |
| | PLAN. RISER SHOWS 2 FSC'S IN HYG #1, AND THE FUTURE DL |
| | & FSC IN OFFICE #1 SHALL BE PIPED THE SAME AS IN THE |
| | OTHER EXAM ROOMS AS THE FLOOR PLAN IS THE SAME FOR ALL |
| | ROOMS. PLEASE CORRELATE RISER & FLOOR PLAN. SECTION |
| | 106.1.1. |
| | |
| | 5. SHT 3 WATER RISER DIAGRAM, IDENTYFY FITTINGS AT THE |
| | TOP OF ALL DROPS AS THEY ARE NOT IDENTIFIED ON THE |
| | SYMBOL LEGEND ON SHT 1. SECTION 106.1.1.--A WATER |
| | HAMMER ARRESTOR IS REQUIRED ON THE ICE MAKER IN THE |
| | LOUNGE AND THE WASHER IN THE STERILE ROOM AS WELL AS |
| | ANY OTHER FIXTURE WITH A QUICK CLOSING VALVE. SECTION |
| | 604.9. WHA'S SHALL BE INSTALLED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE", NOT IN THE CEILING. PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS. |
| | |
| | 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO |
| | THE OFFICE AND SHALL BE INSTALLED A MAXIMUM OF 4' AFF |
| | FOR SERVICE AND CERTIFICATION. SECTION 608.13.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |