| Plan Review Notes For Permit 07020266 |
| Permit Number |
07020266 |
|
| Review Stop |
MEDGAS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-10 17:34:05 | DENIED | | | REFERENCE: NFPA 99C 2002 | | | FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. 1. AIR COMPRESSORS AND VACUUM PUMPS SHALL BE | | | INSTALLED IN A DESIGNATED MECHANICAL EQUIPMENT AREA, | | | VENTILATED AND WITH REQUIRED UTILITIES (E.G., | | | ELECTRICITY, DRAINS, LIGHTING, ETC.). SUBMIT A DETAIL | | | SHOWING THE COMPRESSOR & VACUUM AND ALL OTHER | | | REQUIREMENTS AS DESCRIBED. SECTION 5.3.3..3.7.1. | | | | | | 2. SUBMIT A DETAIL FOR THE COMPRESSOR SHOWING | | | COMPLIANCE WITH SECTION 5.3.3.5.3 (1) THRU (17). (SEE | | | ATTACHED SHEET - FIGURE A.5.3.3.4). | | | | | | 3. SUBMIT A DETAIL FOR THE VACUUM SHOWING COMPLIANCE | | | WITH SECTION 5.3.3.6 AND ALL SUBSECTIONS. (SEE ATTACHED | | | SHEET - FIGURES A.5.3.3.6(A),A5.3.3.6(B), | | | A5.3.3.6(C), OR A5.3.3.6(D). | | | | | | 4. THE EXHAUST VENT FOR THE VACUUM SHALL TERMINATE | | | SEPARATELY ABOVE THE ROOF TO OPEN AIR. SECTION 713.6. | | | | | | 5. SHT 3 AIR/VACUUM INDICATES A 1/2" FILTERED WATER | | | LINE TO THE VACUUM. PLEASE CLARIFY. SECTION 106.1.1. | | | | | | 6. SHT 3 SHOWS WSF (FILTER). THE FILTER SHALL COMPLY | | | WITH NSF 42. SECTION 611.1. PLEASE SUBMIT MANUF. | | | SPECIFICATION SHEETS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|