| Date |
Text |
| 2007-03-01 07:05:18 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST |
| | ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| | 8TH, 2006. |
| | 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS |
| | SUBMITTED |
| | 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED. |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE |
| | STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED |
| | IN THIS REVIEWER(S) COMMENTS. |
| | |
| | 2) NOTE:PLEASE CLARIFY WHAT IS BEING SHOWN ON RISER |
| | OF TWO METERS AND MAINS FOR THIS SINGLE TENANT. PLEASE |
| | KNOW AS THIS IS ONE OCCUPANCY AND ONE TENANT, ONE METER |
| | AND MAIN SHOULD BE SHOWN, HOWEVER IT APPEARS TWO ARE |
| | BEING SHOWN AT THIS TIME?? |
| | PLEASE CLARIFY FBC 106.1.2, 106.3.5.1.2 |
| | 104.6. |
| | PLEASE SEE THIS WOULD ALSO CREATE ZONING AND POSSIBLE |
| | BUILDING ISSUES WITH ONE OCCUPANCY STATED. ONLY ONE |
| | TENANT METER WILL BE PERMITTED BASED ON THE SINGLE |
| | OCCUPANCY AT THIS TIME. |
| | |
| | 3) NOTE: PLEASE 517.60, 517.62 AND OTHER PARTS OF 517. |
| | PLEASE SPECIFY AREAS AND USE IN THESE AREAS. PLEASE |
| | SPECIFY ANY USE OF ANESTHETIZING LOCATIONS IF THIS |
| | APPLIES TO THIS OFFICE AND USE. |
| | NOTES WERE LOCATED FOR TYPE OF WIRING METHODS AND |
| | GROUNDING AS REQUIRED. |
| | |
| | 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE |
| | PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE |
| | ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. |
| | PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION. |
| | |
| | 5) NOTE: PLEASE SHOW LOAD CALCULATIONS ON THE EXISTING |
| | SERVICE (800 AMP DISCONNECT) NEC 220 |
| | PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER |
| | 215.3, AND 230.42 PLEASE INDICATE THE SIZE OF WHAT IS |
| | BEING SHOWN FOR THE EXISTING PANEL AND LOAD ON PANEL |
| | ALONG WITH NEW LOADS. |
| | |
| | |
| | 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT |
| | CORRELATE WITH THE PLANS. PLEASE SEE THE LIGHTING, |
| | WATTAGE, NUMBER OF FIXTURES ETC. |
| | PLEASE BE SURE THE FIXTURE LEGEND STATES THE AMOUNT OF |
| | LIGHTS FOR EACH TYPE OF FIXTURE SPECIFIED AND |
| | COORDINATE THIS WITH THE ENERGY CALCULATIONS. THESE DO |
| | NOT CORRELATE AT ALL AT THIS TIME. |
| | PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS A |
| | NOTE STATED ON PLANS, HOWEVER DOES NOT SEEM TO |
| | CORRELATE WITH ACTUAL PLANS AND CALCULATIONS |
| | SUBMITTED. |
| | PLEASE ALSO SEE USE ENTERED IN AS *SALES AREA*?? PLEASE |
| | SEE THE TABLE IN THE FBC CHAPTER 13 FOR USES. PLEASE BE |
| | SURE THESES CONTAIN A RAISED SEAL, DATE AND SIGNATURE |
| | OF THE DESIGNER OF RECORD. PLEASE SEE THE SEAL IS NOT |
| | VISIBLE WITH INFORMATION ON SAID SEAL AS REQUIRED UNDER |
| | FS 481.221. |
| | PLEASE SEE THE CONTROL METHODS ON THE ENERGY |
| | CALCULATIONS DO NOT CORRELATE WITH PLANS. |
| | PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1, |
| | 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, 13-415.2 |
| | ETC. |
| | |
| | 7) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| | PLANS/LEGEND. |
| | |
| | 8) NOTE: PLEASE SEE THERE ARE SEVERAL FIXTURES ON PLANS |
| | WITHOUT DESIGNATIONS, PLEASE INCLUDE FOR REVIEW OF |
| | CHAPTER 13 REQUIREMENTS. |
| | PLEASE ALSO SEE 13-415.1.ABC.3 WHERE APPLICABLE. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |