| Plan Review Notes For Permit 07020257 |
| Permit Number |
07020257 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-13 08:17:01 | | | | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | PER ARTICLE 220.43(B), AN ADDITIONAL 150 VA OF LOAD IS | | | ADDEDPER 2' OF TRACK. THEREFORE THE LOAD FOR 48 FEET | | | OF TRACK WOULD BE 30 AMPS, REQUIRING TWO BRANCH | | | CIRCUITS. PLEASE INDICATE THE AVAILABLE CIRCUITS ON THE | | | PLAN. | | | | | | THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | | AMENDED. | | | | | | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY | | | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|