Date Text
2007-02-13 08:17:01 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 PER ARTICLE 220.43(B), AN ADDITIONAL 150 VA OF LOAD IS
 ADDEDPER 2' OF TRACK. THEREFORE THE LOAD FOR 48 FEET
 OF TRACK WOULD BE 30 AMPS, REQUIRING TWO BRANCH
 CIRCUITS. PLEASE INDICATE THE AVAILABLE CIRCUITS ON THE
 PLAN.
  
 THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718