| Plan Review Notes For Permit 07020242 |
| Permit Number |
07020242 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-03-05 16:29:39 | BUILDING REVIEW THIRD CHECKLIST: | | | 1- CALCULATED WIND PRESSURES ARE TOO LOW. SEE FIGURE | | | 6-3 ASCE 7-02.WHAT'S THE EFFECTIVE WIND AREA USED FOR | | | THE CALCULATIONS?.ENGINEER NEEDS TO USE AT LEAST 10SF | | | OF EFFECTIVE WIND AREA.SEE EFFECTIVE WIND AREA | | | DEFINITION ON SEC. 1609.2 FBC 2004. | | | | | | 2- IF USING WIND PRESSURE OF -89PSF FOR ENTIRE ROOF, | | | THEN PROVIDEDFASTENER SPACINGDOESN'T WORK.PROVIDE | | | RAS 117 CALCULATIONS.SEC. 106.1.2 CITY AMENDMENTS TO | | | FBC 2004. CLARIFY WHERE WAS THE -89PSF WIND PRESSURE | | | TAKEN FROM?.IT HAS NOTHING TO DO WITH CALCULATED | | | WIND PRESSURES.SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | 3- PROVIDE THE ENGINEERING FIRM CERTIFICATE OF | | | AUTHORIZATION NUMBER IN ALL SHEETS AS REQUIRED BY SEC. | | | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. | | | | | | 4- ENGINEER SEAL IS NOT LEGIBLE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|