2007-03-05 16:29:39BUILDING REVIEW THIRD CHECKLIST:
 1- CALCULATED WIND PRESSURES ARE TOO LOW. SEE FIGURE
 6-3 ASCE 7-02.WHAT'S THE EFFECTIVE WIND AREA USED FOR
 THE CALCULATIONS?.ENGINEER NEEDS TO USE AT LEAST 10SF
 OF EFFECTIVE WIND AREA.SEE EFFECTIVE WIND AREA
 DEFINITION ON SEC. 1609.2 FBC 2004.
  
 2- IF USING WIND PRESSURE OF -89PSF FOR ENTIRE ROOF,
 THEN PROVIDEDFASTENER SPACINGDOESN'T WORK.PROVIDE
 RAS 117 CALCULATIONS.SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004. CLARIFY WHERE WAS THE -89PSF WIND PRESSURE
 TAKEN FROM?.IT HAS NOTHING TO DO WITH CALCULATED
 WIND PRESSURES.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 3- PROVIDE THE ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER IN ALL SHEETS AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 4- ENGINEER SEAL IS NOT LEGIBLE.
  