| 2007-02-12 13:09:50 | BUILDING REVIEW SECOND CHECKLIST: | | | 1-SELECTED ASSEMBLY ON PAGE 38 OF NOA 03-0827.02 HAS | | | A MAXIMUM DESIGN PRESSURE OF -60PSF.UPLIFT PRESSURES | | | AT CORNER AREAS ARE HIGHER. SEE TABLE 1609.6.2.1(2) FBC | | | 2004.THEREFORE, NEED TO PROVIDE RAS 117 CALCULATIONS | | | FOR NAIL ENHANCING AT CORNER AREAS. ACCORDING TO | | | GENERAL LIMITATION #7 OF NOA SUBMITTED THESE | | | CALCULATIONS SHALL BE PREPARED, SINGED AND SEALED ONLY | | | BYARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT. | | | SEE LAST PAGE OF NOA SUBMITTED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|