2007-02-12 13:09:50BUILDING REVIEW SECOND CHECKLIST:
 1-SELECTED ASSEMBLY ON PAGE 38 OF NOA 03-0827.02 HAS
 A MAXIMUM DESIGN PRESSURE OF -60PSF.UPLIFT PRESSURES
 AT CORNER AREAS ARE HIGHER. SEE TABLE 1609.6.2.1(2) FBC
 2004.THEREFORE, NEED TO PROVIDE RAS 117 CALCULATIONS
 FOR NAIL ENHANCING AT CORNER AREAS. ACCORDING TO
 GENERAL LIMITATION #7 OF NOA SUBMITTED THESE
 CALCULATIONS SHALL BE PREPARED, SINGED AND SEALED ONLY
 BYARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT.
 SEE LAST PAGE OF NOA SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER