Plan Review Notes
Plan Review Notes For Permit 07020194
Permit Number 07020194
Review Stop M
Sequence Number 5
Notes
Date Text
2007-11-14 15:34:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION TO PAGE M2.1.
 *** DENIED ***
 1) THE EXHAUST MAY NOT TERMINATE WITHIN 10 FT. OF AN
 INTAKE OPENING, SEE 2004 FBC/M 401.5.1. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved