| Plan Review Notes For Permit 07020194 |
| Permit Number |
07020194 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-08-28 17:33:07 | 2007-08-28 17:33:07 | | | | | | ** DENIED 4TH REVIEW** | | | | | | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED | | | STATES THE METHOD OF CONTROLS AS *MANUAL ON/OFF* WHICH | | | IS NOT POSSIBLE WHEN LIGHTING ON PLANS ARE AUTOMATED. | | | PLEASE OBTAIN NEW ENERGY CALCULATIONS WITH THE CORRECT | | | METHODS CHOSEN TO COORDINATE WITH THE PLANS AND | | | CONTROLS SHOWN. | | | PLEASE KNOW THE OPTIONS ARE ON THE FORMS WHEN DATA IS | | | BEING CHOSEN. | | | PLEASE ALSO SEE THE CERTIFICATION SHEETS ALSO NEED THE | | | OWNER AGENT TO SIGN SHEETS. | | | 13-103.1.1.1, 13-415.C.1 (AS SUBMITTED) | | | | | | ** IF NEW ENERGY CALCULATIONS CAN BE BROUGHT IN AS SOON | | | AS POSSIBLE, THIS WOULD HELP ALLEVIATE ANY RESUBMISSION | | | OF PLANS AND DELAYING POSSIBLE ISSUANCE OF PERMIT IF | | | ALL OTHER TRADES ARE OK. | | | PLEASE KNOW AS NEW ENERGY CALCULATIONS WERE SUBMITTED, | | | THE MECHANICAL REVIEWER WILL STILL REVIEW FOR CODE | | | COMPLIANCE. IF NO CHANGES ARE NEEDED FOR MECH REVIEW, | | | THEN ONLY ADDRESS THIS ABOVE COMMENT AT THIS TIME. | | | | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|