Plan Review Notes
Plan Review Notes For Permit 07020194
Permit Number 07020194
Review Stop E
Sequence Number 4
Notes
Date Text
2007-08-28 17:33:072007-08-28 17:33:07
  
 ** DENIED 4TH REVIEW**
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 STATES THE METHOD OF CONTROLS AS *MANUAL ON/OFF* WHICH
 IS NOT POSSIBLE WHEN LIGHTING ON PLANS ARE AUTOMATED.
 PLEASE OBTAIN NEW ENERGY CALCULATIONS WITH THE CORRECT
 METHODS CHOSEN TO COORDINATE WITH THE PLANS AND
 CONTROLS SHOWN.
 PLEASE KNOW THE OPTIONS ARE ON THE FORMS WHEN DATA IS
 BEING CHOSEN.
 PLEASE ALSO SEE THE CERTIFICATION SHEETS ALSO NEED THE
 OWNER AGENT TO SIGN SHEETS.
 13-103.1.1.1, 13-415.C.1 (AS SUBMITTED)
  
 ** IF NEW ENERGY CALCULATIONS CAN BE BROUGHT IN AS SOON
 AS POSSIBLE, THIS WOULD HELP ALLEVIATE ANY RESUBMISSION
 OF PLANS AND DELAYING POSSIBLE ISSUANCE OF PERMIT IF
 ALL OTHER TRADES ARE OK.
 PLEASE KNOW AS NEW ENERGY CALCULATIONS WERE SUBMITTED,
 THE MECHANICAL REVIEWER WILL STILL REVIEW FOR CODE
 COMPLIANCE. IF NO CHANGES ARE NEEDED FOR MECH REVIEW,
 THEN ONLY ADDRESS THIS ABOVE COMMENT AT THIS TIME.
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  