Plan Review Notes
Plan Review Notes For Permit 07020194
Permit Number 07020194
Review Stop E
Sequence Number 3
Notes
Date Text
2007-07-02 18:27:082007-07-02 18:27:08
 ** UNSAT3RD REVIEW**
 ** 1ST REVIEW UNDER PERMIT APPLICATION**
  
 ** PLEASE SEE THERE ARE NOTES FROM THE PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW NOTES.
  
  
 1) NOTE: *** IMPORTANT***
 PLEASE DO NOT ATTACHED SUPPORTING DOCUMENTS DOWN THE
 LEFT SIDE OF PLANS. THESE SHOULD BE PLACED INTO TWO
 SETS, FOLDER(S), SPIRAL NOTEBOOK, OR SOME OTHER FASHION
 TO KEEP TOGETHER. THESE WERE REMOVED FROM PLANS.
  
 2) NOTE PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ARCHITECT AND THE ARCHITECTURAL
 FIRM.PLEASE SEE THE TITLE COVER SHEETS WHICH STILL
 INDICATE ERIC HAFER AND ASSOCIATES PA.
 RESPONSES MENTIONS THAT THIS WAS BEING REMOVED ON ALL
 SHEETS, HOWEVER THIS STILL SHOWN.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FLORIDA STATUES 481.219
 * THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE REVIEWER.
  
 3) NOTE: PLEASE SEE NEW SIGNED, DATED AND SEALED SHEETS
 BY THE ENGINEER FOR ELECTRICAL WHICH THE RAISED SEALS
 ARE NOT CLEAR AND VISIBLE. PLEASE SEE THE PREVIOUS
 SHEETS DATED APRIL 07 WERE OK, HOWEVER EVEN USING A
 LEAD DUST RUB ON SEALS, THE INFORMATION WHICH IS
 REQUIRED TO BE CLEAR AND VISIBLE IS NOT.
 PLEASE SEE FS 471.025, FAC 61G15-23.001.
  
 4) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 IS
 STILL IN QUESTION:
 PLEASE SEE SEVERAL CIRCUITS AS NOTED ON PLANS FOR LE,
 26, 28 AND 30 WHICH DO NOT SEEM TO SHOW ANY LIGHTING
 CONTROLS, OVER RIDES OR PART OF THE LCP.?
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 OF THE FBC
 CHAPTER 13.
 ** PLEASE SEE NOTES ON PLANS MENTIONS SOME ITEMS AND
 SOME CONTROLS HOWEVER NOT ALL INFORMATION FOR MINIMUM
 DESIGN FOR CODE IS PRESENT.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE IN
 FACT THE SAME AS PREVIOUSLY SUBMITTED. PLEASE SEE THE
 DESIGN WATTAGE IS STILL HIGHER THAN THE ALLOWANCE.
 PLEASE SEE THE VERSION IS STILL NOT CORRECT. PLEASE SEE
 ALL VERSIONS WITH AN EFFECTIVE DATE AS OF DECEMBER 8TH,
 2006. PLEASE SEE THE 2.1 IS NO LONGER IN EFFECT. PLEASE
 SEE THE INPUT DATA REPORTS ARE NOW NO LONGER ATTACHED.
 **AS PREVIOUSLY NOTED**
 PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS PER 13-415.AB.1.1, 13-415.1.A, 13-415.1.B,
 13-415.1.C, 13-415.2
 PLEASE SEE 13-103.1.1.1 FOR DESIGNER OF RECORD TO SIGN,
 DATE AND SEAL SAID DOCUMENTS.
  
 5) NOTE:PLEASE SEE DETAIL/RISER NOTE ON TRANSFORMER
 STILL STATES TO SEE THE SHEET E1.1 AND DETAIL 05 FOR
 GROUNDING OF TRANSFORMER WHICH IS BLANK. THE RESPONSE
 MENTIONS THIS IS TO BE CORRECTED AND SEE OTHER SHEET
 HOWEVER RISER WAS NOT ADJUSTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE ATTACHMENT LOCATION FOR THE NEW
 TRANSFORMER.
 PLEASE SEE THE RESPONSE LETTER MENTIONS TO SEE REVISED
 SINGLE LINE DIAGRAM WHICH SAYS TO SEE DETAIL #5 ON
 SHEET 1.1, HOWEVER THIS DETAIL #5 IS ACTUALLY BLANK ON
 SHEET 1.1.
 PLEASE COORDINATE PLANS AND POSSIBLE DETAIL ON SHEET
 1.5.
 PLEASE SEE 250.50, 250.30, 250.20.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-02 17:06:272007-07-02 17:06:27
 PLANS REMOVED FROM INCOMING, PLANS WILL BE SENT BACK TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS DONE.