| Date |
Text |
| 2007-07-02 18:27:08 | 2007-07-02 18:27:08 |
| | ** UNSAT3RD REVIEW** |
| | ** 1ST REVIEW UNDER PERMIT APPLICATION** |
| | |
| | ** PLEASE SEE THERE ARE NOTES FROM THE PREVIOUS REVIEW |
| | WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW NOTES. |
| | |
| | |
| | 1) NOTE: *** IMPORTANT*** |
| | PLEASE DO NOT ATTACHED SUPPORTING DOCUMENTS DOWN THE |
| | LEFT SIDE OF PLANS. THESE SHOULD BE PLACED INTO TWO |
| | SETS, FOLDER(S), SPIRAL NOTEBOOK, OR SOME OTHER FASHION |
| | TO KEEP TOGETHER. THESE WERE REMOVED FROM PLANS. |
| | |
| | 2) NOTE PLEASE SEE MISSING INFORMATION REQUIRED ON |
| | TITLE BLOCKS FOR THE ARCHITECT AND THE ARCHITECTURAL |
| | FIRM.PLEASE SEE THE TITLE COVER SHEETS WHICH STILL |
| | INDICATE ERIC HAFER AND ASSOCIATES PA. |
| | RESPONSES MENTIONS THAT THIS WAS BEING REMOVED ON ALL |
| | SHEETS, HOWEVER THIS STILL SHOWN. |
| | PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 |
| | AND FLORIDA STATUES 481.219 |
| | * THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE REVIEWER. |
| | |
| | 3) NOTE: PLEASE SEE NEW SIGNED, DATED AND SEALED SHEETS |
| | BY THE ENGINEER FOR ELECTRICAL WHICH THE RAISED SEALS |
| | ARE NOT CLEAR AND VISIBLE. PLEASE SEE THE PREVIOUS |
| | SHEETS DATED APRIL 07 WERE OK, HOWEVER EVEN USING A |
| | LEAD DUST RUB ON SEALS, THE INFORMATION WHICH IS |
| | REQUIRED TO BE CLEAR AND VISIBLE IS NOT. |
| | PLEASE SEE FS 471.025, FAC 61G15-23.001. |
| | |
| | 4) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 IS |
| | STILL IN QUESTION: |
| | PLEASE SEE SEVERAL CIRCUITS AS NOTED ON PLANS FOR LE, |
| | 26, 28 AND 30 WHICH DO NOT SEEM TO SHOW ANY LIGHTING |
| | CONTROLS, OVER RIDES OR PART OF THE LCP.? |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 OF THE FBC |
| | CHAPTER 13. |
| | ** PLEASE SEE NOTES ON PLANS MENTIONS SOME ITEMS AND |
| | SOME CONTROLS HOWEVER NOT ALL INFORMATION FOR MINIMUM |
| | DESIGN FOR CODE IS PRESENT. |
| | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE IN |
| | FACT THE SAME AS PREVIOUSLY SUBMITTED. PLEASE SEE THE |
| | DESIGN WATTAGE IS STILL HIGHER THAN THE ALLOWANCE. |
| | PLEASE SEE THE VERSION IS STILL NOT CORRECT. PLEASE SEE |
| | ALL VERSIONS WITH AN EFFECTIVE DATE AS OF DECEMBER 8TH, |
| | 2006. PLEASE SEE THE 2.1 IS NO LONGER IN EFFECT. PLEASE |
| | SEE THE INPUT DATA REPORTS ARE NOW NO LONGER ATTACHED. |
| | **AS PREVIOUSLY NOTED** |
| | PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE |
| | CALCULATIONS PER 13-415.AB.1.1, 13-415.1.A, 13-415.1.B, |
| | 13-415.1.C, 13-415.2 |
| | PLEASE SEE 13-103.1.1.1 FOR DESIGNER OF RECORD TO SIGN, |
| | DATE AND SEAL SAID DOCUMENTS. |
| | |
| | 5) NOTE:PLEASE SEE DETAIL/RISER NOTE ON TRANSFORMER |
| | STILL STATES TO SEE THE SHEET E1.1 AND DETAIL 05 FOR |
| | GROUNDING OF TRANSFORMER WHICH IS BLANK. THE RESPONSE |
| | MENTIONS THIS IS TO BE CORRECTED AND SEE OTHER SHEET |
| | HOWEVER RISER WAS NOT ADJUSTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE ATTACHMENT LOCATION FOR THE NEW |
| | TRANSFORMER. |
| | PLEASE SEE THE RESPONSE LETTER MENTIONS TO SEE REVISED |
| | SINGLE LINE DIAGRAM WHICH SAYS TO SEE DETAIL #5 ON |
| | SHEET 1.1, HOWEVER THIS DETAIL #5 IS ACTUALLY BLANK ON |
| | SHEET 1.1. |
| | PLEASE COORDINATE PLANS AND POSSIBLE DETAIL ON SHEET |
| | 1.5. |
| | PLEASE SEE 250.50, 250.30, 250.20. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-02 17:06:27 | 2007-07-02 17:06:27 |
| | PLANS REMOVED FROM INCOMING, PLANS WILL BE SENT BACK TO |
| | INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW |
| | IS DONE. |