| 2007-04-24 19:05:23 | |
| | |
| | ** UNSAT2ND REVIEW** |
| | |
| | ** PLEASE SEE THERE ARE NOTES FROM THE PREVIOUS REVIEW |
| | WHICH STILL NEED TO BE ADDRESSED ALONG WITH NEW NOTES. |
| | |
| | |
| | |
| | 1) NOTE:SAME NOTE. |
| | PLEASE SEE THAT PLANS HAVE ONLY BEEN SUBMITTED FOR * |
| | PLAN REVIEW* AND NOT SUBMITTED FOR PERMIT APPLICATION. |
| | PLEASE KNOW PLANS WILL REMAIN IN *F* STATUS FOR ALL |
| | TRADES EVEN IF PLANS ARE OK. PERMIT APPLICATION FOR |
| | SCOPE OF WORK, VALUE, RELEVANT CODES ETC WILL NEED TO |
| | BE VERIFIED ONCE APPLICATION IS MADE. |
| | |
| | 2) NOTE:SAME NOTE. PLEASE SEE THERE ARE SEVERAL AREAS |
| | WHERE THE INCORRECT CODES ARE REFERENCED. PLEASE SEE |
| | THE STATE OF FLORIDA IS NOT UNDER THE IEC OR THE 1997 |
| | SOUTH FLORIDA ENERGY CODE. |
| | PLEASE SEE PLANS WHICH ARE REDLINED AT MANY OF THE |
| | LOCATIONS WHICH STILL INDICATE THESE. |
| | PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED |
| | CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| | 8TH, 2006. |
| | 2004 FBC W/ 2006 REVISION. (THIS WILL AFFECT PLANS |
| | SUBMITTED). |
| | 2005 NFPA-70 (NEC). (THIS WILL AFFECT PLANS AS NUMEROUS |
| | LOCATIONS REFLECT CODES FROM THE 1999 NFPA-70.) 2002 |
| | NFPA-72 |
| | 2003 NFPA-101 |
| | ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE |
| | REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR |
| | REVIEWER(S). |
| | PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH |
| | REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD |
| | BE REVISED ACCORDINGLY. |
| | |
| | 3) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON |
| | TITLE BLOCKS FOR THE ARCHITECT AND THE ARCHITECTURAL |
| | FIRM.THIS IS THE SAME COMMENT AS PREVIOUS REVIEW AS |
| | NO LICENSE INFORMATION FOR ERIC HAFER AND ASSOCIATES PA |
| | HAS BEEN SHOWN. |
| | PLEASE SEE THE MISSING FIRM LICENSE NUMBER WHICH IS |
| | ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION NUMBER |
| | AND ALSO THE MISSING PRINTED NAME AND PRINTED LICENSE |
| | NUMBER OF THE ARCHITECT. |
| | PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 |
| | AND FLORIDA STATUES 481.219 |
| | * THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE REVIEWER. |
| | |
| | 4) NOTE: PLEASE SEE THE PREVIOUS NOTES WITH RESPECT TO |
| | CHAPTER 13. PLEASE SE THE LIGHTING ZONES AS SUBMITTED |
| | ALONG WITH THE SCHEDULE TABLES DOES NOT SEEM TO BE |
| | COMPLETE. MOST IS BLANK? PLEASE CLARIFY. |
| | PLEASE SEE SOME OF THE AREAS AND ROOMS DO NOT INDICATE |
| | ANY CONTROL DEVICES FOR AUTOMATED CONTROL OF LIGHTING |
| | AND THE PROPOSED ZONED LIGHTING SYSTEM DOES NOT PROVIDE |
| | ENOUGH INFORMATION. |
| | PLEASE SEE THE SYMBOL LEGEND SHOULD COORDINATE WITH THE |
| | SYMBOLS TO BE SHOWN ON PLANS. |
| | PLEASE SHOW ALL DEVICES/OCCUPANCY SENSORS ON PLANS. |
| | (COVERAGE NEEDS TO BE REVIEWED FOR LOCATIONS ETC) |
| | PLEASE BE SURE TO COORDINATE THE DEVICES AS SHOWN AND |
| | TO BE SHOWN ON THE LIGHTING CONTROL SHEETS WITH THAT OF |
| | THE LIGHTING PLANS. PLEASE UPDATE AND REVISE ALL |
| | DEVICES AND LOCATIONS. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED UNDER |
| | METHOD *C* IS NOT CLEAR HOW THE DESIGN WATTAGE AS SHOWN |
| | IS SO MUCH HIGHER THAN THE EFFECTIVE AND THE |
| | ALLOWANCE. |
| | PLANS STILL INDICATES THE INCORRECT CODES AS REQUIRED |
| | AND NOTED IN NOTE #1 AND THIS NOTE FROM PREVIOUS |
| | REVIEW. |
| | PLEASE ADJUST AND PLEASE PROVIDE MORE SPECIFICATIONS ON |
| | PLEASE SEE THE ENERGY CODE AS STATED ON PLANS IS NOT |
| | THE 2004 FBC W/ 2006 REVISIONS TO CHAPTER 13. THE STATE |
| | OF FLORIDA CONTAINS ITS OWN ENERGY CODE. PLEASE SEE THE |
| | PLANS STATE THE 1997 ENERGY CODE ALONG WITH THE 2004 |
| | IEC. |
| | PLEASE SUBMIT THE INFORMATION RELEVANT TO THE 2004 FBC |
| | AND 2006 REVISIONS FOR LIGHTING CONTROLS AND LOCATIONS |
| | PER 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE THAT SOME DEVICES ON PLANS APPEAR TO CONTROL |
| | LIGHTING, HOWEVER DOES NOT PROVIDE INFORMATION ON TYPE |
| | AND OVER RIDE TIMES. SOME DEVICES ARE NOTED ON PLANS |
| | AND TIMES ARE SHOWN, HOWEVER COVERAGE DOES NOT SEEM TO |
| | BE PROVIDED FOR SOME OTHER AREAS. |
| | PLEASE SEE NOTE ON PLANS WHICH MENTIONS HALLWAY |
| | LIGHTING AND CONTROLS ARE NOTED AS EXISTING TO REMAIN, |
| | HOWEVER THIS DOES NOT SEEM TO CORRELATE WITH THE OTHER |
| | WORK AS SHOWN ON PLANS. |
| | PLEASE CLARIFY HOW THE FIGURES AS SHOWN ON PLANS |
| | INDICATE A SWITCH ON THE LOAD SIDE OF THE POWER PACK. |
| | HOW WILL THESE DEVICES REACT ON AN AUTOMATIC BASIS WHEN |
| | AN OCCUPANT ENTERS AN AREA IF A SWITCH IS IN THE OFF |
| | POSITION? PLEASE ALSO SEE ANOTHER SCENARIO, WHERE A |
| | ROOM OR AREA IS OCCUPIED, SOMEONE LEAVES AND TURNS THE |
| | SWITCH OFF, THEN THIS WOULD LEAVE ANY OF THE OTHER |
| | OCCUPANTS IN DARKNESS ?? |
| | PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE |
| | CALCULATIONS PER 13-415.AB.1.1, 13-415.1.A, 13-415.1.B, |
| | 13-415.1.C, 13-415.2 |
| | PLEASE SEE 13-103.1.1.1 FOR DESIGNER OF RECORD TO SIGN, |
| | DATE AND SEAL SAID DOCUMENTS. |
| | |
| | 5) NOTE: NOTES WERE ADDED TO PLANS FOR VERIFICATION, |
| | HOWEVER THIS INFORMATION SHOULD BE OBTAINED FROM THE |
| | SITE AND PLACED ON PLANS ACCORDINGLY. |
| | ** PREVIOUS NOTE ** PLEASE VERIFY NEW OR EXISTING |
| | EMERGENCY LIGHTING OUTSIDE EXIT DOOR TO STAIR AREA AND |
| | DOOR LOCATED TO THE PUBLIC RIGHT OF WAY. IF EXISTING, |
| | PLEASE SHOW, IF NOT EXISTING, NEW WILL BE REQUIRED. |
| | PLEASE SEE 2003 NFPA-101 7.8, 7.9 |
| | |
| | 6) NOTE:PLEASE INDICATE THE ATTACHMENT LOCATION FOR |
| | THE NEW TRANSFORMER. |
| | PLEASE SEE THE RESPONSE LETTER MENTIONS TO SEE REVISED |
| | SINGLE LINE DIAGRAM WHICH SAYS TO SEE DETAIL #5 ON |
| | SHEET 1.1, HOWEVER THIS DETAIL #5 IS ACTUALLY BLANK ON |
| | SHEET 1.1. |
| | PLEASE COORDINATE PLANS AND POSSIBLE DETAIL ON SHEET |
| | 1.5. |
| | PLEASE SEE 250.50, 250.30, 250.20. |
| | |
| | 7) NOTE: PLEASE CLARIFY TAPPED CONDUCTORS FROM GUTTER |
| | TO EACH OF THE 150A MCB DISCONNECTS AS SHOWN ON RISER |
| | ON THE SECONDARY SIDE OF THE TRANSFORMER. |
| | 240.21, 310.16, 240.4 |
| | |
| | 8) NOTE: PLEASE KNOW THAT THE LOW VOLTAGE AS SHOWN ON |
| | PLANS WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. LV |
| | SECURITY IS UNDER A SEPARATE PERMIT FROM OTHER LV |
| | WORK. |
| | PLANS PERMIT APPLICATIONS AND FEES WILL BE DUE FOR |
| | THESE SYSTEMS AS NOTED. IF THERE ARE ANY QUESTIONS ON |
| | THIS, PLEASE CALL TO GO OVER. |
| | |
| | ** PLEASE KNOW THAT DUE TO SOME INFORMATION NOT |
| | SUBMITTED AT THIS TIME, REVIEW OF SOME ITEMS FOR CODE |
| | COMPLIANCE CAN NOT BE DONE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |