| Plan Review Notes For Permit 07020194 |
| Permit Number |
07020194 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-27 12:30:21 | ** FOR PLAN REVIEW, NOT FOR PERMIT ** | | | *** DENIED *** | | | 1) CERTIFICATE OF AUTHORIZATION NUMBER FOR THE | | | ENGINEERING BUSINESS (POLARIS) MUST APPEAR IN THE TITLE | | | BLOCK, SEE FAC 61G15-23.002. | | | | | | 2) THE 34X16 RETURN AIR TRANSFER DUCT FROM CLASSROOM | | | 107 TO SHAMPOO 103 IS PENETRATING FIRE RATED WALLS AND | | | WILL NEED FIRE DAMPERS, SEE 2004 FBC/M 607.5.2. ALSO | | | PLEASE EXPLAIN WHAT ( --- CBBC ) IS, I COULD NOT FIND | | | IN THE ABBREVIATIONS. | | | | | | 3) THE 9" SUPPLY AIR DUCT FROM THE CORRIDOR TO THE | | | BOOKSTORE 116 WILL NEED A FIRE DAMPER ALSO, SEE 2004 | | | FBC/M 607.5.3, 2, 2.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|