| 2007-03-19 16:24:13 | *****DENIED***** |
| | |
| | |
| | |
| | 1. NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| | PREVENTION CODE (2004) EDITION) SHALL BE REFERENCED. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| | NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO |
| | THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE |
| | LANES). |
| | |
| | 4.PLEASE INDICATE IF THE BUILDING OR PORTIONS OF THE |
| | BUILDING WILL BE OCCUPIED DURING THE PROPOSED SCOPE OF |
| | WORK.IF SO,THIS WILL BE PERMITTED ONLY WHERE |
| | REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION |
| | FEATURES ARE IN PLACE AND MAINTAINED, OR WHERE |
| | ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE AHJ |
| | ARE IN PLACE. |
| | |
| | 5.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL |
| | BE CLASS A OR CLASS B IN EXITS AND EXIT ACCESS |
| | CORRIDORS,CLASS A, CLASS B, OR CLASS C IN ALL OTHER |
| | AREAS.PLEASE SPECIFY. |
| | |
| | 6.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES |
| | THE TRAVEL DISTANCE TO THE EXIT(S).ALSO INDICATE THE |
| | LOCATION OF THE 2A:10BC FIRE EXTINGUISHERS WHICH |
| | SATISFY THE 75 ' TRAVEL DISTANCE REQUIREMENT. |
| | |
| | 7.IF THE EXISTING FIRE ALARM AND/OR FIRE SPRINKLER |
| | SYSTEM IS/ARE MODIFIED DUE TO THE SCOPE OF WORK, |
| | SEPARATE PLANS AND PERMIT WILL BE REQUIRED. |
| | |
| | 8.PLEASE NOTE THE DIFFERENCE IN THE LAYOUT OF THE |
| | FACIAL ROOM [116] ON SHEET E-2.2 AND E-2.6 COMPARED TO |
| | E-2.1 ANDE-2.3. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RE-SUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| | ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |