Plan Review Notes
Plan Review Notes For Permit 07020194
Permit Number 07020194
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-03-19 16:24:13*****DENIED*****
  
  
  
 1. NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004) EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO
 THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.PLEASE INDICATE IF THE BUILDING OR PORTIONS OF THE
 BUILDING WILL BE OCCUPIED DURING THE PROPOSED SCOPE OF
 WORK.IF SO,THIS WILL BE PERMITTED ONLY WHERE
 REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN PLACE AND MAINTAINED, OR WHERE
 ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE AHJ
 ARE IN PLACE.
  
 5.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL
 BE CLASS A OR CLASS B IN EXITS AND EXIT ACCESS
 CORRIDORS,CLASS A, CLASS B, OR CLASS C IN ALL OTHER
 AREAS.PLEASE SPECIFY.
  
 6.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).ALSO INDICATE THE
 LOCATION OF THE 2A:10BC FIRE EXTINGUISHERS WHICH
 SATISFY THE 75 ' TRAVEL DISTANCE REQUIREMENT.
  
 7.IF THE EXISTING FIRE ALARM AND/OR FIRE SPRINKLER
 SYSTEM IS/ARE MODIFIED DUE TO THE SCOPE OF WORK,
 SEPARATE PLANS AND PERMIT WILL BE REQUIRED.
  
 8.PLEASE NOTE THE DIFFERENCE IN THE LAYOUT OF THE
 FACIAL ROOM [116] ON SHEET E-2.2 AND E-2.6 COMPARED TO
 E-2.1 ANDE-2.3.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RE-SUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722