| 2007-02-21 18:01:52 | *** UNSAT *** |
| | |
| | |
| | 1) NOTE:PLEASE SEE THAT PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR * PLAN REVIEW* AND NOT SUBMITTED FOR |
| | PERMIT APPLICATION. PLEASE KNOW PLANS WILL REMAIN IN |
| | *F* STATUS FOR ALL TRADES EVEN IF PLANS ARE OK. PERMIT |
| | APPLICATION FOR SCOPE OF WORK, VALUE, RELEVANT CODES |
| | ETC WILL NEED TO BE VERIFIED ONCE APPLICATION IS MADE. |
| | |
| | 2) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST |
| | ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| | 8TH, 2006. |
| | 2004 FBC W/ 2006 REVISION. (THIS WILL AFFECT PLANS |
| | SUBMITTED). |
| | 2005 NFPA-70 (NEC). (THIS WILL AFFECT PLANS AS NUMEROUS |
| | LOCATIONS REFLECT CODES FROM THE 1999 NFPA-70.) 2002 |
| | NFPA-72 |
| | 2003 NFPA-101 |
| | ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE |
| | REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR |
| | REVIEWER(S). |
| | PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH |
| | REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD |
| | BE REVISED ACCORDINGLY. |
| | |
| | 3) NOTE: PLEASE SEE MISSING THE REQUIRED RAISED SEALED |
| | FROM THE ARCHITECT OF RECORD PER FLORIDA ADMINISTRATIVE |
| | CODE 61G1-16.003, FLORIDA STATUES 481.221. THE USE OF A |
| | *RUBBER STAMP* IS NOT PERMITTED IN THE STATE OF |
| | FLORIDA. |
| | * THIS IS REQUIRED FOR ALL SHEETS AND WHETHER OR NOT |
| | COMMENT IS MADE BY ANY OTHER REVIEWER. |
| | |
| | 4) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON |
| | TITLE BLOCKS FOR THE ARCHITECT AND THE ARCHITECTURAL |
| | FIRM. PLEASE SEE THE MISSING FIRM LICENSE NUMBER WHICH |
| | IS ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER AND ALSO THE MISSING PRINTED NAME AND PRINTED |
| | LICENSE NUMBER OF THE ARCHITECT. |
| | PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 |
| | AND FLORIDA STATUES 481.219 |
| | * THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE REVIEWER. |
| | |
| | 5) NOTE: PLEASE SEE THE MISSING LICENSE INFORMATION FOR |
| | THE ENGINEERING FIRM. PLEASE SEE THE MISSING |
| | CERTIFICATE OF AUTHORIZATION NUMBER PER FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUES |
| | 471.023. |
| | * THIS IS REQUIRED FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 6) NOTE: PLEASE SEE THE SEAL USED ON SOME SHEETS FOR |
| | THE ENGINEER OF RECORD IS LONGER VALID FOR USE IN THE |
| | STATE OF FLORIDA. PLEASE SEE THAT THE WORDING OF |
| | *CERTIFICATE* IN SEAL WAS REQUIRED TO BE CHANGED TO THE |
| | WORDING OF *LICENSE* IN FEB 04. THE RULE 61G15-23.001 |
| | WAS EXTENDED TO DECEMBER 31ST, 2005 HOWEVER ALL PLANS |
| | AFTER THAT DATE MAY NOT USE THE OLD SEAL. THIS IS ONLY |
| | THE CASE ON SOME OF THE SHEETS IN ONE OF THE SETS |
| | SUBMITTED. PLEASE CORRECT. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | |
| | 7) NOTE: PLEASE SEE THE ENERGY CODE AS STATED ON PLANS |
| | IS NOT THE 2004 FBC W/ 2006 REVISIONS TO CHAPTER 13. |
| | THE STATE OF FLORIDA CONTAINS ITS OWN ENERGY CODE. |
| | PLEASE SEE THE PLANS STATE THE 1997 ENERGY CODE ALONG |
| | WITH THE 2004 IEC. |
| | PLEASE SUBMIT THE INFORMATION RELEVANT TO THE 2004 FBC |
| | AND 2006 REVISIONS FOR LIGHTING CONTROLS AND LOCATIONS |
| | PER 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE THAT SOME DEVICES ON PLANS APPEAR TO CONTROL |
| | LIGHTING, HOWEVER DOES NOT PROVIDE INFORMATION ON TYPE |
| | AND OVER RIDE TIMES. SOME DEVICES ARE NOTED ON PLANS |
| | AND TIMES ARE SHOWN, HOWEVER COVERAGE DOES NOT SEEM TO |
| | BE PROVIDED FOR SOME OTHER AREAS. |
| | PLEASE SEE NOTE ON PLANS WHICH MENTIONS HALLWAY |
| | LIGHTING AND CONTROLS ARE NOTED AS EXISTING TO REMAIN, |
| | HOWEVER THIS DOES NOT SEEM TO CORRELATE WITH THE OTHER |
| | WORK AS SHOWN ON PLANS. |
| | PLEASE CLARIFY HOW THE FIGURES AS SHOWN ON PLANS |
| | INDICATE A SWITCH ON THE LOAD SIDE OF THE POWER PACK. |
| | HOW WILL THESE DEVICES REACT ON AN AUTOMATIC BASIS WHEN |
| | AN OCCUPANT ENTERS AN AREA IF A SWITCH IS IN THE OFF |
| | POSITION? PLEASE ALSO SEE ANOTHER SCENARIO, WHERE A |
| | ROOM OR AREA IS OCCUPIED, SOMEONE LEAVES AND TURNS THE |
| | SWITCH OFF, THEN THIS WOULD LEAVE ANY OF THE OTHER |
| | OCCUPANTS IN DARKNESS ?? |
| | PLEASE SUBMIT ENERGY CALCULATIONS/PERFORMANCE |
| | CALCULATIONS PER 13-415.AB.1.1, 13-415.2 |
| | PLEASE SEE 13-103.1.1.1 FOR DESIGNER OF RECORD TO SIGN, |
| | DATE AND SEAL SAID DOCUMENTS. |
| | |
| | 8) NOTE: PLEASE SEE THAT THE COLOR CODING FOR 277/480V |
| | SYSTEMS SHALL BE BROWN, PURPLE, YELLOW. PLEASE KNOW |
| | SYSTEMS LOCATED IN THE CITY OF WEST PALM BEACH ARE |
| | CURRENTLY UNDER THIS COLOR CODING FOR FEEDERS DUE TO |
| | PREVIOUS LOCAL AMENDMENTS. |
| | * PER NEC, *ORANGE* COLOR IS FOR A HIGH-LEG OF DELTA |
| | SYSTEM. |
| | FBC ADMIN SECTION 104.6 |
| | |
| | 9) NOTE: PLEASE SPECIFY THE MINIMUM LEVELS FOR HORN AND |
| | STROBE DEVICES ON PLANS. IT IS KNOW THAT THERE WILL BE |
| | SEPARATE PERMIT FOR ANY FIRE ALARM SYSTEM OR DEVICE |
| | WORK; HOWEVER THE BASE PLANS ARE REQUIRED TO SHOW THIS |
| | INFORMATION AT THIS TIME. PLEASE SEE FBC 11-4.28.1, .2, |
| | AND .3(4) FOR MINIMUM LEVELS TO BE ON PLANS. |
| | |
| | 10) NOTE: PLEASE SEE THE MAIN ELECTRICAL ROOM EVEN AS |
| | EXISTING IS INDICATING THE DOOR SWING INWARDS. PLEASE |
| | VERIFY THIS. PLEASE SEE 110.26 OF THE NEC. |
| | PLEASE SEE THAT THE DOOR SWING IS REQUIRED TO SWING |
| | OUT. PLEASE ADJUST. DUE TO THE LEVEL OF WORK AND |
| | ALTERATION, DOOR SWING WILL BE REQUIRED TO BE CHANGED |
| | IF NOT ALREADY IN THE SWING OUT POSITION. PLEASE BE |
| | SURE TO SEE POSSIBLE SWING AND TRAVEL OF DOOR SWING IN |
| | EXIT CORRIDOR. PLEASE SEE THAT THE DOOR SWING MAY BE |
| | REQUIRED TO OPEN IN THE PATH OF EGRESS AND ON 180 |
| | DEGREE HINGES? PLEASE ALSO SEE OTHER MAXIMUM DOOR WIDTH |
| | IN HALL WHEN IN OPEN POSITION. THIS MAY NOT BE A |
| | BUILDING REVIEW COMMENT AT THIS TIME, HOWEVER AS THE |
| | DOOR SWING WILL BE REQUIRED TO BE CHANGED, AND THEN |
| | PLEASE BE SURE TO CHECK WITH BUILDING CODE FOR |
| | ALLOWANCES. |
| | ** THIS IS A LIFE SAFETY ISSUE FOR EXITING FROM THE |
| | ELECTRICAL ROOM DURING AN EMERGENCY. |
| | |
| | 11) NOTE: PLEASE VERIFY NEW OR EXISTING EMERGENCY |
| | LIGHTING OUTSIDE EXIT DOOR TO STAIR AREA AND DOOR |
| | LOCATED TO THE PUBLIC RIGHT OF WAY. IF EXISTING, PLEASE |
| | SHOW, IF NOT EXISTING, NEW WILL BE REQUIRED. PLEASE SEE |
| | 2003 NFPA-101 7.8, 7.9 |
| | |
| | 12) NOTE: PLEASE INDICATE THE ATTACHMENT LOCATION FOR |
| | THE NEW TRANSFORMER. |
| | PLEASE SEE 250.50, 250.30, 250.20. |
| | |
| | 13) NOTE: PLEASE SEE 250.66 FOR THE CORRECT SIZING OF |
| | THE GROUNDING ELECTRODE CONDUCTOR FOR THE TRANSFORMER. |
| | |
| | 14) NOTE: PLEASE SEE THE FEEDERS ON THE RISER SHOW A |
| | NEUTRAL CONDUCTOR FROM THE MDP TO THE NEW TRANSFORMER. |
| | HOW IS THIS POSSIBLE WHEN THIS IS A SEPARATELY DERIVED |
| | SYSTEM AND THE TRANSFORMER CREATES ITS OWN NEW NEUTRAL |
| | POINT? |
| | PLEASE CLARIFY. |
| | 250.20, 250.30 ETC |
| | |
| | 15) NOTE: PLEASE PROVIDE A MORE DETAILED LOAD SUMMARY. |
| | : LOADS ARE CURRENTLY SHOWN AT CONNECTED LOADS FOR |
| | ALL. |
| | PLEASE SEE 220.12, 220.14, 220.42, 220.44 ETC. PLEASE |
| | INDICATE ALL CONTINUOUS LOADS AT 125%. 215.3, 230.42. |
| | |
| | 16) NOTE: PLEASE NOTE OR PROVIDE INFORMATION IF THE |
| | EXISTING MAIN AT 277/480 AND OVER 1000AMPS CONTAINS GF |
| | PROTECTION. |
| | 240.13, 230.95 ONLY NEEDS TO NOTE IF EXISTING. |
| | |
| | ** PLEASE KNOW THAT DUE TO SOME INFORMATION NOT |
| | SUBMITTED AT THIS TIME, REVIEW OF SOME ITEMS FOR CODE |
| | COMPLIANCE CAN NOT BE DONE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-02-19 10:10:00 | IN ELEC FOR REVIEW. |