Plan Review Notes
Plan Review Notes For Permit 07020189
Permit Number 07020189
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-03-21 17:57:43*****DENIED*****
  
 ATTENTION:UNLESS OTHERWISE NOTED, THIS STRUCTURE
 SHALL BE CLASSIFIED AS A NEW STORAGE OCCUPANCY.
  
  
  
 01.NFPA 101- 2003 EDITION SHALL BE REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION. ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.THE ERECTING AND (OR) INSTALLATION OF THE STORAGE
 ADDITION SHALL NOT INTERFERE OR HINDER EMERGENCY ACCESS
 TO THE PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 05.INDICATE THE CLASSIFICATION OF CONTENTS TO BE
 STORED AS LOW HAZARD, INTERMEDIATE HAZARD, OR HIGH
 HAZARD DEPENDING ON THE CHARACTER OF THE MATERIALS
 STORED, THEIR PACKAGING, AND OTHER FACTORS.
  
 06.PROVIDE THE OCCUPANT LOAD OR MAXIMUM PROBABLE
 POPULATION FOR THIS SPACE UNDER CONSIDERATION.
  
 07.PROVIDE THE INTERIOR WALL AND CEILING
 CLASSIFICATION.PLEASE BE ADVISED THAT CLASS A, CLASS
 B, OR CLASS C SHALL BE REQUIRED FOR STORAGE AREAS AND
 EXIT ENCLOSURES.PLEASE SPECIFY WHICH CLASSIFICATION.
  
 08.SHOW THE LOCATION OF THE EXIT LIGHT(S) AND
 EMERGENCY LIGHT(S).
  
 09.WILL THE STRUCTURE HAVE A FIRE SPRINKLER AND (OR)
 FIRE ALARM SYSTEM?
  
 10.INDICATE THE LOCATION OF THE2A:10BC FIRE
 EXTINGUISHER(S).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW