| Date |
Text |
| 2008-04-08 10:50:42 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) ENERGY CALCULATIONS LINE 12A SHOWS A 17 SEER A/C |
| | SYSTEM, PLEASE PROVIDE EQUIPMENT MODEL NUMBERS TO |
| | VERIFY, PER 2004 FBC 13-607.1.ABC.3.1.1. |
| | |
| | 2) ENERGY CALCULATIONS LINE 12B SHOWS A 16.5 SEER A/C |
| | SYSTEM, MECHANICAL PLANS SHOW THE SYSTEM TO BE 14.5 |
| | SEER, THE TWO MUST COINCIDE, PLEASE CORRECT. |
| | |
| | 3) ENERGY CALCULATION LINE 13A AND B SHOW THE A/C |
| | SYSTEMS TO BE HEAT PUMP UNITS, PLEASE PROVIDE CORRECT |
| | MODEL NUMBERS FOR BOTH SYSTEMS TO VERIFY, PER 2004 FBC |
| | 13-101.4.2.1. |
| | |
| | 4) ENERGY CALCULATIONS LINE 14A SHOWS THE WATER HEATER |
| | IS NATURAL GAS, ELECTRICAL PLAN PAGE 7 STATES THE WATER |
| | HEATER IS ELECTRIC, THE TWO MUST COINCIDE, PLEASE |
| | CORRECT. |
| | |
| | 5) COOLING LOAD CALCULATIONS FOR A/C SYSTEM #2 ARE |
| | CALLING FOR 34,119 TOTAL COOLING BTU'S, THE MECHANICAL |
| | PLANS SHOWING THE SYSTEM TO BE 42,500 TOTAL COOLING |
| | BTU'S. THE PLANS CAN ONLY CALL FOR 15% MORE THAN THE |
| | COOLING LOAD CAL'S, A 3.5 TON A/C SYSTEM IS TO LARGE |
| | PLEASE CORRECT, PER 2004 FBC 13-607.1.ABC.1.1. |
| | |
| | 6)THE A/C SYSTEM LISTED ON THE MECHANICAL PLAN A/C |
| | EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI |
| | DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI |
| | CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |