2008-04-08 10:50:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 12A SHOWS A 17 SEER A/C
 SYSTEM, PLEASE PROVIDE EQUIPMENT MODEL NUMBERS TO
 VERIFY, PER 2004 FBC 13-607.1.ABC.3.1.1.
  
 2) ENERGY CALCULATIONS LINE 12B SHOWS A 16.5 SEER A/C
 SYSTEM, MECHANICAL PLANS SHOW THE SYSTEM TO BE 14.5
 SEER, THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 3) ENERGY CALCULATION LINE 13A AND B SHOW THE A/C
 SYSTEMS TO BE HEAT PUMP UNITS, PLEASE PROVIDE CORRECT
 MODEL NUMBERS FOR BOTH SYSTEMS TO VERIFY, PER 2004 FBC
 13-101.4.2.1.
  
 4) ENERGY CALCULATIONS LINE 14A SHOWS THE WATER HEATER
 IS NATURAL GAS, ELECTRICAL PLAN PAGE 7 STATES THE WATER
 HEATER IS ELECTRIC, THE TWO MUST COINCIDE, PLEASE
 CORRECT.
  
 5) COOLING LOAD CALCULATIONS FOR A/C SYSTEM #2 ARE
 CALLING FOR 34,119 TOTAL COOLING BTU'S, THE MECHANICAL
 PLANS SHOWING THE SYSTEM TO BE 42,500 TOTAL COOLING
 BTU'S. THE PLANS CAN ONLY CALL FOR 15% MORE THAN THE
 COOLING LOAD CAL'S, A 3.5 TON A/C SYSTEM IS TO LARGE
 PLEASE CORRECT, PER 2004 FBC 13-607.1.ABC.1.1.
  
 6)THE A/C SYSTEM LISTED ON THE MECHANICAL PLAN A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]