2007-12-18 15:36:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE NEW ENERGY CALCULATIONS SUBMITTED ARE THE WRONG
 FORM, NEED TO SUBMIT THE 2004R FORM, PER 2004 FBC
 13-600.3.A. (THE SHORT FORM 600C-04R MAY BE SUBMITTED
 FOR THE ADDITION INSTEAD OF THE LONG FORM, SEE
 13-600.3C.)
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY PREPARER
 AND OWNER/AGENT, PER 2004 FBC 13-600.3.ABC.2.
  
 3) THE COOLING LOAD CALCULATIONS SUBMITTED HAVE NOT
 BEEN CALCULATED CORRECTLY, THE WHOLE HOUSE CALCULATIONS
 ARE CALLING FOR 234,478 TOTAL BTU'S THAT WOULD BE 19.5
 TONS OF AIR CONDITIONING FOR 1,238 SQUARE FEET OF
 LIVING SPACE. SUBMIT CORRECTED COOLING LOAD
 CALCULATIONS, PLEASE HAVE SHEETS IN CORRECT ORDER AND
 STAPLED, SEE 2004 FBC 13-607.1.ABC.1. ONLY NEED COOLING
 LOAD CALCULATIONS FOR THE ADDITION IF NO MECHANICAL
 WORK IS TO BE DONE TO THE EXISTING PART OF THE HOUSE
 AND THE A/C SYSTEM AND DUCT WORK IS TO REMAIN AS THE
 PLANS SHOW.
  
 4) PLEASE SHOW MECHANICAL PLAN PAGE 8, HOW THE AIR FROM
 THE RETURN AIR JUMPER BOX WILL RETURN TO THE AIR
 HANDLER IF THE DOOR IS CLOSED TO THE MEDIA ROOM, SEE
 2004 FBC/R M1602.4.
  
 5) PLEASE SHOW THE CORRECT MODEL NUMBER FOR THE A/C
 CONDENSER UNIT IN THE A/C SCHEDULE ON THE MECHANICAL
 PLAN, SEE 2004 FBC 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]