| 2007-12-20 16:59:18 | RESIDENTIAL ADDITION, BUILDING REVIEW THIRD CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2006 REVISIONS. |
| | |
| | 1- CONNECTORSPECIFIED ON SHEET 11 FOR THE END OF |
| | GIRDER TRUSSES RESTING ON THE MASONRY WALL IS |
| | INCORRECT. IT DOESN'T MATCH CONDITIONS SHOWN ON PLANS. |
| | HOW CAN YOU BOLT THE STEEL CONNECTOR TO THE CONCRETE |
| | COLUMN?.ALSO, THERE IS NOT TIE BEAM BELOW GIRDER |
| | TRUSS. PROVIDE CORRECT DETAIL.SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004 TOVERIFY COMPLIANCE WITH THE |
| | DESIGN LOADS OF SEC. R301 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 2- OWES $1.66 FOR RADON FEES. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR:ALLSIMPSON OR USP STRUCTURAL CONNECTORS |
| | SPECIFIED ON ENGINEER PLANS. (REPEAT COMMENT). |
| | INFORMATION SUBMITTED IS NOT AN APPROVEDPRODUCT |
| | APPROVALBUT A COPY FROM THE MANUFACTURER'SCATALOG. |
| | PROVIDE PROPERFLORIDA PRODUCT APPROVAL COVER PAGE AND |
| | PAGE WHERE CONNECTOR IS SHOWN ONLY.NO NEED TO PROVIDE |
| | COMPLETE CONNECTORS REPORT TO SAVE PAPER.GO TO |
| | WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING |
| | INFORMATION. |
| | |
| | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | LETTER FROMENGINEER STATING THAT HE REVIEW THE |
| | PRODUCT APPROVAL IS NOT ACCEPTABLE BECAUSE IT DOESN'T |
| | SPECIFY WHICH SPECIFIC PRODUCT APPROVALS WERE REVIEWED. |
| | ENGINEER OF RECORD TO USETHE STANDARD REVIEW AND |
| | APPROVED STAMP ON EACH PRODUCT APPROVAL OR PROVIDE |
| | LETTER WHICH IDENTIFIES EACH SPECIFIC PRODUCT APPROVAL |
| | OR NOA NUMBER REVIEWED. |
| | |
| | 5- TRUSS DRAWINGS: ALL ENGINEERING DETAILS, LETTERS, |
| | ETC.NEED TO BE SIGNED, SEALED, DATED AND HAVE ALL THE |
| | ENGINEER'S INFORMATION AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTES AND SEC. 61G15-23.002 OF FLORIDA |
| | ADMINISTRATIVE CODE. (REPEAT COMMENT). |
| | |
| | 6- NEW ENERGY CALCULATIONS WERE SUBMITTED: |
| | A) PROVIDE CURRENT UPDATED FORM 600A-2004R. SEE |
| | MECHANICAL PLAN REVIEWER COMMENTS. |
| | |
| | B) PREPARER TO SIGN AND DATE FORM. |
| | |
| | C) OWNER/AGENT TO SIGN AND DATE THE FORM. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |