2007-09-26 14:29:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLANS SUBMITTED PAGE 8 (MECHANICAL PLAN) NOW SHOWS A
 NEW A/C SYSTEM FOR THE OFFICE. COOLING LOAD
 CALCULATIONS (MANUAL J) IS FOR THE WHOLE HOUSE BUT
 NEEDS TO BE FOR THE OFFICE ONLY. PLEASE SUBMIT COOLING
 LOAD CALCULATIONS (MANUAL J) FOR THE OFFICE ONLY. SEE
 2004 FBC 13-607.1.ABC.1.
  
 2) ENERGY CALCULATIONS LINE 6 SHOWS CONDITIONED FLOOR
 AREA AS 1243 SQUARE FEET, IF THE ENERGY CALCULATIONS
 ARE FOR THE WHOLE HOUSE THEN THEY NEED TO SHOW THE TWO
 A/C SYSTEMS EXISTING AND NEW AND ALL INFORMATION NEEDS
 TO BE ADJUSTED SHOWING ALL THE EXISTING AND NEW
 CONDITIONS OF THE HOUSE. PLEASE REVISE ENERGY
 CALCULATIONS, SEE FBC 13-101.2.2.
  
 ** IF YOU WISH YOU MAY SUBMIT ENERGY CALCULATIONS FORM
 600C-04R FOR THE ADDITION ONLY, SEE FBC 13-600.3.C.
  
 3) PLANS PAGE 8 A/C UNIT SCHEDULE NEEDS TO SHOW THE
 CONDENSER UNIT MODEL NUMBER ALSO, SEE W.P.B. AMEND.
 106.3.5.4 (10).
  
 4) PLANS PAGE 8 AHU DETAIL SHOWS THE AUXILIARY DRAIN
 LINE GOING BELOW THE SLAB. SEE 2004 FBC/R M1411.3.1 #1
 THE AUXILIARY DRAIN MUST DISCHARGE TO A CONSPICUOUS
 POINT OF DISPOSAL, OR YOU MAY COMPLY WITH #3. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]