Plan Review Notes
Plan Review Notes For Permit 07020178
Permit Number 07020178
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-01 18:17:24RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC
 2004 WITH 2006 REVISIONS.
  
 1-OWES $404.00 FOR UPDATED PERMIT VALUATION AS
 REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 2- ATTIC ACCESS SHOWN ON PLANS DOESN'T WORK. SEE ROOF
 FRAMING PLANFOR ORIENTATION OF TRUSSES. ALSO,THERE
 IS NOT HEADROOM IF ATTIC ACCESS IS TOO CLOSE TO THE
 EXTERIOR WALL. REVISE AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 3- ROOF TILE WAS CHANGED TO ROOF SHINGLES. REVISE
 ORIGINAL DRAWINGS. CROSSING OUT PRINTS BY HAND IS NOT
 ALLOWED.
 IN ADDITION ENGINEER'S SIGNATURE DOESN'T MATCH
 SIGNATURE SHOWN BY ENGINEER'S SEAL..
  
 4- SPECIFY CONNECTORS AT THE OTHER END OF WALL GIRDERS
 RESTING ON MASONRY WALL. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004 (REPEAT COMMENT).
  
 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ALL STRUCTURAL TRUSS CONNECTORS SPECIFIED ON
 PLANS.INFORMATION SUBMITTED IS A COPY OF FROM THE USP
 CATALOG, NOT A PRODUCT APPROVAL. PROVIDE ONLY THE
 PRODUCT APPROVAL COVER PAGE ANDPAGE WHERE SPECIFIED
 CONNECTORS ARE SHOWN TO SAVE TIME AND PAPER.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004
 (REPEAT COMMENT).
  
 7- TRUSS DRAWINGS:
 A) ALL GENERAL DRAWINGS, DETAILS, SPECS, LETTERS,
 ETC. NEED TO HAVE ENGINEER'SORIGINAL SEAL, SIGNATURE
 AND DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE. IN
 ADDITION ALL SHEETS NEED TO HAVE THE ENGINEER'S
 COMPLETEINFORMATION AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002 (REPEAT
 COMMENT).
  
 8- FOUNDATION DESIGN BEARING CAPACITY NOTE ON SHEET #6
 CALLS FOR 2500 PSF SOIL BEARING CAPACITY, WHILEPAGE
 ONE OF SOIL TEST REPORT CALLS FOR 2000PSF SOIL BEARING
 CAPACITY. REVISE AS REQUIRED TOMATCH.(REPEAT
 COMMENT).
  
 9- PROVIDE 2 COPIES OF SOIL TEST REPORT WITH ORIGINAL
 ENGINEER'S SIGNATURE AND SEAL.ONLY ONE WAS
 SUBMITTED.
  
 10- HURRICANE STRAP SCHEDULE.REVISE NUMBER OF NAILS
 SPECIFIED FOR TAPL16 CONNECTOR.SEE PRODUCT APPROVAL
 FOR CORRECT NUMBER OF NAILS. OTHERWISE PROVIDE COMPLETE
 ENGINEERING ANALYSISIF NUMBER OF NAILS DIFFER FROM
 THOSE TESTED AND PUBLISHED BY THE MANUFACTURER.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 (REPEAT COMMENT).
  
 11- CLARIFY HANGER DETAIL TO CONCRETE COLUMN ON SHEET
 #11. WHERE IS THIS DETAIL TAKEN PLACE AT? . HOW IS THE
 PLATE WELDED TO CONCRETE COLUMN?. HOW ARE THE THRU
 BOLTS INSTALLED?. SEC. 106.1.2 CITY AMENDMENTSTO FBC
 2004.
  
 12- PROVIDE ONLY DETAILS THAT APPLY TO THIS JOB TO
 EXPEDITE REVIEW PROCESS AND AVOID CONFLICTS.
  
 13- NOTICE OF COMMENCEMENT WAS RECORDED ON 02/07/2007.
 THIS DOCUMENT EXPIRES IF WORK IS NOT STARTED WITHIN 90
 DAYS OF RECORDING IT. THEREFORE, NEED RE-RECORDED
 NOTICE OF COMMENCMENT AS REQUIRED BY SEC. 713.13
 FLORIDA STATUTE.
  
 NOTE:
 PROVIDING A CHECKLIST RESPONSE LETTER IS HIGHLY
 RECOMMENDED TOEXPEDITE THE REVIEW PROCESS ANDVERIFY
 THAT ALLITEMS ARE ADDRESSED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712