| 2007-03-08 11:25:10 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY |
| | OF WEST PALM BEACH AMENDMENTS; |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET 4 PLUMBING PLAN INDICATES ASTUB OUT FOR |
| | FUTURE SINK:PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| | FUTURE SINK WASTE, VENT, TRAP AND SIZES WITH CLEANOUT |
| | LOCATIONS. |
| | |
| | 2. PER FBC-2004 PLUMBING, SECTION 704.4 FUTURE |
| | FIXTURES: DRAINAGE PIPING FOR FUTURE FIXTURES SHALL |
| | TERMINATE WITH AN APPROVED CAP OR PLUG. PLEASE INDICATE |
| | THIS ON THE RESUBMITTAL. |
| | |
| | 3. PER FBC-2004 PLUMBING, SECTION 905.6 VENT FOR FUTURE |
| | FIXTURE: WHERE THE DRAINAGE PIPING HAS BEEN ROUGHED-IN |
| | FOR THE FUTURE FIXTURE, A ROUGH-IN CONNECTION FOR A |
| | VENT SHALL BE INSTALLED. THE VENT SIZE SHALL NOT BE |
| | LESS THAN ONE-HALF THE DIAMETER OF THE ROUGH-IN DRAIN |
| | TO BE SERVED. THE VENT ROUGH-IN SHALL CONNECT TO THE |
| | VENT SYSTEM, OR SHALL BE VENTED BY OTHER MEANS AS |
| | PROVIDED FOR IN THIS CHAPTER. THE CONNECTION SHALL BE |
| | IDENTIFIED TO INTICATE THAT IT IS A VENT. PLEASE COMPLY |
| | ON THE RESUBMITTAL. |
| | |
| | IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |