Plan Review Notes
Plan Review Notes For Permit 07020178
Permit Number 07020178
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-08 11:25:10DENIED
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 4 PLUMBING PLAN INDICATES ASTUB OUT FOR
 FUTURE SINK:PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 FUTURE SINK WASTE, VENT, TRAP AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 2. PER FBC-2004 PLUMBING, SECTION 704.4 FUTURE
 FIXTURES: DRAINAGE PIPING FOR FUTURE FIXTURES SHALL
 TERMINATE WITH AN APPROVED CAP OR PLUG. PLEASE INDICATE
 THIS ON THE RESUBMITTAL.
  
 3. PER FBC-2004 PLUMBING, SECTION 905.6 VENT FOR FUTURE
 FIXTURE: WHERE THE DRAINAGE PIPING HAS BEEN ROUGHED-IN
 FOR THE FUTURE FIXTURE, A ROUGH-IN CONNECTION FOR A
 VENT SHALL BE INSTALLED. THE VENT SIZE SHALL NOT BE
 LESS THAN ONE-HALF THE DIAMETER OF THE ROUGH-IN DRAIN
 TO BE SERVED. THE VENT ROUGH-IN SHALL CONNECT TO THE
 VENT SYSTEM, OR SHALL BE VENTED BY OTHER MEANS AS
 PROVIDED FOR IN THIS CHAPTER. THE CONNECTION SHALL BE
 IDENTIFIED TO INTICATE THAT IT IS A VENT. PLEASE COMPLY
 ON THE RESUBMITTAL.
  
 IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  