Plan Review Notes
Plan Review Notes For Permit 07020178
Permit Number 07020178
Review Stop M
Sequence Number 1
Notes
Date Text
2007-03-05 11:35:15*** DENIED ***
 1) NEED TO SHOW THE SIZE OF THE SUPPLY AIR DUCT FROM
 THE EXISTING A/C TO THE MIXING BOX.
  
 2) THE 10" RETURN AIR TRANSFER DUCT FOR THE OFFICE NEED
 TO BE 14", SEE 2004 FBC/R M1602.4.
  
 *** 2004 FBC/R M1602.4.
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.