| Plan Review Notes For Permit 07020178 |
| Permit Number |
07020178 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-05 11:35:15 | *** DENIED *** | | | 1) NEED TO SHOW THE SIZE OF THE SUPPLY AIR DUCT FROM | | | THE EXISTING A/C TO THE MIXING BOX. | | | | | | 2) THE 10" RETURN AIR TRANSFER DUCT FOR THE OFFICE NEED | | | TO BE 14", SEE 2004 FBC/R M1602.4. | | | | | | *** 2004 FBC/R M1602.4. | | | BALANCED RETURN AIR MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|