Plan Review Notes
Plan Review Notes For Permit 07020178
Permit Number 07020178
Review Stop B
Sequence Number 1
Notes
Date Text
2007-03-27 17:52:39BUILDING REVIEW CHECKLIST:
 1- ENGINEER'S NAME DOESN'T MATCHNAME THAT APPEARS ON
 EMBOSSED SEAL.. CLARIFY/REVISE AS REQUIRED.
  
 2- TOTAL ADDITION AREA IS INCORRECT. REVISE AS
 REQUIRED. SEE DIMENSIONSON PLANS.
  
 3- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5115) AFTER PLANS ARE REVISED WITH CORRECT NEW
 ADDITION AREA TO CHECK IF ADDITIONAL IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND PAID RECEIPT IF
 ADDITIONAL FEES ARE DUE.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW.ALSO, NEED TO CONSIDER WINDOWS AND DOORS
 REPLACEMENT AND DEMOLITION COSTS. UPDATE VALUE OR IT
 WILL ESTIMATED AS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004.
  
 5- SPECIFY ATTIC ACCESSIN NEW ADDITION AS REQUIRED BY
 SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 6- PROVIDE DETAIL/SECTION FOR FOOTING A.FOOTING
 SCHEDULE TYPE AND REMARKS CALL FOR STEM TYPE FOOTING,
 WHILE FOUNDATION PLANS SHOWS MONOLITHIC TYPE. REVISE AS
 REQUIRED.
  
 7- PROVIDE COMPLETE DETAILS,SECTIONS, SPECS FOR
 CUPOLA CONSTRUCTION. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 8- DESIGNER OF RECORD TO SPECIFY SPECIFIC ROOF TILE
 FASTENING AS REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS
 TO FBC 2004.PRODUCT APPROVAL IS TO SHOW COMPLIANCE
 WITH DESIGNER OF RECORD SPECS.
  
 9- PROVIDE COMPLETE DETAIL AT TOP OF STEEL COLUMN
 RECEIVING THE TWO WALL GIRDERS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 10- PROVIDE COMPLETE SPECS FOR BOTTOM PLATE OF STEEL
 COLUMN. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 11- SPECIFY CONNECTORS AT THE OTHER ENDS OF WALL
 GIRDERS RESTING ON MASONRY WALL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 12- PLEASE PROVIDE ONLY THE DETAILS AND SPECS THAT
 APPLY TO THIS PROJECT TO EXPEDITE THE REVIEW PROCESS.
  
 13- SPECIFY DESIGN PRESSURES FOR WINDOWS AND DOORS TO
 BE REPLACED TO VERIFY PRODUCT APPROVAL COMPLIANCE. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) WINDOW MULLIONS.
  
 B) TRUSS STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
  
 C) GARAGE DOOR.
  
 D) ROOF TILE. NOA #01-0417.09 SUBMITTED EXPIRED ON
 06/07/2006. NEED CURRENT ONE.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 SUBMITTED AS REQUIRED BYSEC. 106.3.3CITY AMENDMENTS
 TO FBC 2004.
  
 16- TRUSS DRAWINGS:
 A) TRUSS LOADING CONDITIONS SHOWN ON TRUSS LAYOUT
 SHEET DON'T MATCH LOADING ON INDIVIDUAL TRUSSES. REVISE
 AS REQUIRED.
  
 B) ENGINEER TO USE SEAL THAT SAYS LICENSE NOT
 CERTIFICATE.
  
 C) WIND LOAD CRITERIA DOESN'T MATCH SPECIFICATIONS
 SHOWN ON DRAWING #6 OF CONSTRUCTION DOCUMENTS.REVISE
 AS REQUIRED.
  
 D) ALL GENERAL DRAWINGS, DETAILS, SPECS, LETTERS
 ETC. NEED TO HAVE ENGINEER'S ORIGINAL SEAL,SIGNATURE
 AND DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
 * IN ADDITION ALL SHEETS NEED TO HAVE THE ENGINEER'S
 COMPLETE INFORMATION AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002.
 ** ALSO, USE SEAL THAT SAYS LICENSE, NOT CERTIFICATE.
  
 17- FOOTING NOTE ON FOOTING SCHEDULE SHEET #6 STATES
 SAFE SOIL BEARING CAPACITY OF 2500 PSF PER SOIL TEST
 REPORT BY EASTCOAST TESTING & ENGINEERING WAS
 CONSIDERED FOR THE ADDITION DESIGN.SOIL TEST REPORT
 FIRST PAGE STATES SOIL BEARING CAPACITY OF 2000 PSF.
 CLARIFY/REVISE AS REQUIRED.
  
 18- HURRICANE STRAP SCHEDULE. SEE CURRENT CATALOG FOR
 SPECIFIC NUMBER OF FASTENERS TO BE USED AND REVISE AS
 REQUIRED. OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSIS IF NUMBER AND TYPE OF FASTENERS DIFFER FROM
 THOSE TESTED AND PUBLISHED BY THE MANUFACTURER. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 19- SHEET #10:
 A) STRUCTURAL BUCK DETAILS. SEE SEC. R613.6.2 OF
 2004 FLORIDA RESIDENTIAL CODE FOR PROPER WAY OF
 INSTALLING DOORS AND WINDOW BUCKS AND REVISE DETAIL AS
 REQUIRED. BEVELED BUCKS ARE NOT ALLOWED AND WINDOW NEED
 COMPLETE FRAME SUPPORT.
  
 B) PROVIDE ONLY DETAILS,SPECSAND NOTES THAT
 APPLY TO THIS PROJECT TO EXPEDITE REVIEW PROCESS AND
 AVOID CODE CONFLICTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712