| 2007-03-27 17:52:39 | BUILDING REVIEW CHECKLIST: |
| | 1- ENGINEER'S NAME DOESN'T MATCHNAME THAT APPEARS ON |
| | EMBOSSED SEAL.. CLARIFY/REVISE AS REQUIRED. |
| | |
| | 2- TOTAL ADDITION AREA IS INCORRECT. REVISE AS |
| | REQUIRED. SEE DIMENSIONSON PLANS. |
| | |
| | 3- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5115) AFTER PLANS ARE REVISED WITH CORRECT NEW |
| | ADDITION AREA TO CHECK IF ADDITIONAL IMPACT FEES ARE |
| | DUE. BRING BACK STAMPED PLANS AND PAID RECEIPT IF |
| | ADDITIONAL FEES ARE DUE. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW.ALSO, NEED TO CONSIDER WINDOWS AND DOORS |
| | REPLACEMENT AND DEMOLITION COSTS. UPDATE VALUE OR IT |
| | WILL ESTIMATED AS REQUIRED BY SEC. 108.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 5- SPECIFY ATTIC ACCESSIN NEW ADDITION AS REQUIRED BY |
| | SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- PROVIDE DETAIL/SECTION FOR FOOTING A.FOOTING |
| | SCHEDULE TYPE AND REMARKS CALL FOR STEM TYPE FOOTING, |
| | WHILE FOUNDATION PLANS SHOWS MONOLITHIC TYPE. REVISE AS |
| | REQUIRED. |
| | |
| | 7- PROVIDE COMPLETE DETAILS,SECTIONS, SPECS FOR |
| | CUPOLA CONSTRUCTION. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 8- DESIGNER OF RECORD TO SPECIFY SPECIFIC ROOF TILE |
| | FASTENING AS REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS |
| | TO FBC 2004.PRODUCT APPROVAL IS TO SHOW COMPLIANCE |
| | WITH DESIGNER OF RECORD SPECS. |
| | |
| | 9- PROVIDE COMPLETE DETAIL AT TOP OF STEEL COLUMN |
| | RECEIVING THE TWO WALL GIRDERS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 10- PROVIDE COMPLETE SPECS FOR BOTTOM PLATE OF STEEL |
| | COLUMN. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 11- SPECIFY CONNECTORS AT THE OTHER ENDS OF WALL |
| | GIRDERS RESTING ON MASONRY WALL. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 12- PLEASE PROVIDE ONLY THE DETAILS AND SPECS THAT |
| | APPLY TO THIS PROJECT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | 13- SPECIFY DESIGN PRESSURES FOR WINDOWS AND DOORS TO |
| | BE REPLACED TO VERIFY PRODUCT APPROVAL COMPLIANCE. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) WINDOW MULLIONS. |
| | |
| | B) TRUSS STRUCTURAL CONNECTORS SPECIFIED ON PLANS. |
| | |
| | C) GARAGE DOOR. |
| | |
| | D) ROOF TILE. NOA #01-0417.09 SUBMITTED EXPIRED ON |
| | 06/07/2006. NEED CURRENT ONE. |
| | |
| | 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| | SUBMITTED AS REQUIRED BYSEC. 106.3.3CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 16- TRUSS DRAWINGS: |
| | A) TRUSS LOADING CONDITIONS SHOWN ON TRUSS LAYOUT |
| | SHEET DON'T MATCH LOADING ON INDIVIDUAL TRUSSES. REVISE |
| | AS REQUIRED. |
| | |
| | B) ENGINEER TO USE SEAL THAT SAYS LICENSE NOT |
| | CERTIFICATE. |
| | |
| | C) WIND LOAD CRITERIA DOESN'T MATCH SPECIFICATIONS |
| | SHOWN ON DRAWING #6 OF CONSTRUCTION DOCUMENTS.REVISE |
| | AS REQUIRED. |
| | |
| | D) ALL GENERAL DRAWINGS, DETAILS, SPECS, LETTERS |
| | ETC. NEED TO HAVE ENGINEER'S ORIGINAL SEAL,SIGNATURE |
| | AND DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. |
| | * IN ADDITION ALL SHEETS NEED TO HAVE THE ENGINEER'S |
| | COMPLETE INFORMATION AS REQUIRED BY FLORIDA |
| | ADMINISTRATIVE CODE SEC. 61G15-23.002. |
| | ** ALSO, USE SEAL THAT SAYS LICENSE, NOT CERTIFICATE. |
| | |
| | 17- FOOTING NOTE ON FOOTING SCHEDULE SHEET #6 STATES |
| | SAFE SOIL BEARING CAPACITY OF 2500 PSF PER SOIL TEST |
| | REPORT BY EASTCOAST TESTING & ENGINEERING WAS |
| | CONSIDERED FOR THE ADDITION DESIGN.SOIL TEST REPORT |
| | FIRST PAGE STATES SOIL BEARING CAPACITY OF 2000 PSF. |
| | CLARIFY/REVISE AS REQUIRED. |
| | |
| | 18- HURRICANE STRAP SCHEDULE. SEE CURRENT CATALOG FOR |
| | SPECIFIC NUMBER OF FASTENERS TO BE USED AND REVISE AS |
| | REQUIRED. OTHERWISE, PROVIDE COMPLETE ENGINEERING |
| | ANALYSIS IF NUMBER AND TYPE OF FASTENERS DIFFER FROM |
| | THOSE TESTED AND PUBLISHED BY THE MANUFACTURER. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 19- SHEET #10: |
| | A) STRUCTURAL BUCK DETAILS. SEE SEC. R613.6.2 OF |
| | 2004 FLORIDA RESIDENTIAL CODE FOR PROPER WAY OF |
| | INSTALLING DOORS AND WINDOW BUCKS AND REVISE DETAIL AS |
| | REQUIRED. BEVELED BUCKS ARE NOT ALLOWED AND WINDOW NEED |
| | COMPLETE FRAME SUPPORT. |
| | |
| | B) PROVIDE ONLY DETAILS,SPECSAND NOTES THAT |
| | APPLY TO THIS PROJECT TO EXPEDITE REVIEW PROCESS AND |
| | AVOID CODE CONFLICTS. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |