| Plan Review Notes For Permit 07020172 |
| Permit Number |
07020172 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-07 16:59:17 | BUILDING REVIEW CHECKLIST: | | | | | | ***NOTE:PROVIDE ALL THE INFORMATION REQUIRED BY CITY | | | POLICY FOR ROOFING PERMITS. SEE ATTACHED COPY. | | | | | | 1-WOOD DECK: | | | A) FROM NOA SUBMITTED,CLEARLY IDENTIFY WHICH | | | APPROVED ASSEMBLY IS GOING TO BE INSTALLED. | | | | | | B) FROM NOA SUBMITTED, CLEARLY IDENTIFYSPECIFIC | | | BASE SHEET FASTENING OPTION. | | | | | | B) FROM NOA SUBMITTED. PROVIDERAS 117 CALCULATIONS | | | FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7. SEE LAST PAGE OF | | | NOA. | | | | | | 2- CONCRETE DECK: | | | A) FROM NOA SUBMITTED, CLEARLY IDENTIFY WHICH | | | APPROVED ASSEMBLY IS GOING TO BE INSTALLED. | | | | | | B) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | | LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS IF | | | ASSEMBLY IS DESIGNED FOR DESIGN PRESSURES LESS THAN | | | THOSE SPECIFIED ON TABLE 1609.6.2.1(2) 2004 FBC. SEE | | | LAST PAGE OF NOA. | | | | | | C) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | | LIMITATION #9, THEN IT MAY NOT BE USED IN THIS AREA IF | | | ASSEMBLY IS DESIGNED FOR DESIGN PRESSURES LESS THAN | | | THOSE SPECIFIED ON TABLE 1609.6.2.1(2) 2004 FBC 2004. | | | NAIL ENHANCING IS NOT ALLOWED IN GENERAL LIMITATION #9. | | | SEE LAST PAGE OF NOA. | | | | | | 3- SEPARATE PERMITS REQUIRED TO REMOVE AND RE-INSTALL | | | ALL ROOF EQUIPMENT. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 | | | |
|