| 2007-02-23 14:10:03 | BUILDING REVIEW THIRD CHECKLIST: |
| | 1- TESTING RESULTS FROM ADVANCED RESEARCH & TESTING |
| | INC.: |
| | A) AS REQUESTED ON PREVIOUS CHECKLIST, PROVIDE |
| | FIRM'S CERTIFICATE OF AUTHORIZATION NUMBER IN ALL |
| | SHEETS AS REQUIRED BY FLORIDA ADMINISTRATIVE CODE SEC. |
| | 61G15-23.00.INFORMATION WAS NOT PROVIDED. FIRM'S |
| | CERTIFICATE OF AUTHORIZATION NUMBER AND ENGINEER'S |
| | LICENSE NUMBER ARE TWO DIFFERENT THINGS. SEE ATTACHED |
| | COPY. |
| | |
| | B) PREVIOUS PACKAGE SUBMITTED DESCRIBED THAT TEST |
| | APPARATUS USED WAS MODEL- FGC-2000 AND SERIAL #2960430. |
| | PACKAGE SUBMITTED THIS TIME DESCRIBED THAT TEST |
| | APPARATUS USED WAS MODEL DFG-2W-2000 AND SERIAL |
| | #20610070. |
| | WHERE TWO DIFFERENT APPARATUS USED?.WHERE BOTH |
| | APPARATUS CALIBRATED?.HOW COME THE FIRST 10 TESTS |
| | HAVE THE SAME READING IF 2 DIFFERENT APPARATUS WERE |
| | USED?. |
| | |
| | ***NOTE: ONE SET OF THESE TESTSRESULTS WILL BE |
| | RETAINDED IN THIS OFFICE TO BE SEND TO THE BOARD OF |
| | ENGINEERS. ENGINEER TO PROVIDE CLARIFICATIONOF THIS |
| | ISSUE TO THE BOARD OF ENGINEERS. |
| | |
| | C) ENGINEER LICENSE NUMBER ON FIRST PAGE OF TEST |
| | REPORT SIGNED AND SEALED ON 2/21/07 IS INCORRECT. |
| | REVISE AS REQUIRED. |
| | |
| | D) CERTIFICATE OF CALIBRATIONSTATES THAT |
| | CALIBRATION DATE WAS 10/30/2006.ACCORDING TO SEC. |
| | 10.1.1 OF TESTING APPLICATION STANDARD (TAS)105-98 THE |
| | "PULL TESTER" SHOULD BE DONE WITHIN THREE MONTHS PRIOR |
| | TO CONDUCTING THE TEST. PROVIDE PROOF OF DATE THAT TEST |
| | WAS PERFORMED TO VERIFY COMPLIANCE WITH THIS TEST |
| | STANDARD. |
| | |
| | 2- A) ENGINEERASSEMBLY ATTACHMENT CALCULATIONS DON'T |
| | MATCH CALCULATIONS SUBMITTED THE FIRST TIME.NOW |
| | CALCULATIONS SHOW MAX. SYSTEM DESIGN PRESSURES OF |
| | -60PSF. BUT,IN NOA 03-0404.05 PAGE 10FASTENING |
| | OPTION #1 WAS CIRCLED.INFORMATION DOESN'T MATCH. |
| | REVISE AS REQUIRED. |
| | |
| | B) CLARIFY WHY IS THE ENGINEER SIGNING AND SEALING |
| | NOA 03-0404.05. HE'S IS NOT ALLOWED TO SING AND SEAL |
| | THIS PRODUCT APPROVAL BECAUSE HE'S NOT THE ENGINEER OF |
| | RECORD RESPONSIBLE FOR THE PRODUCT APPROVAL. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |