| Plan Review Notes For Permit 07020133 |
| Permit Number |
07020133 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-02-20 15:25:08 | BUILDING REVIEW SECOND CHECKLIST: | | | 1- TESTING APPLICATION STANDARD (TAS) 105-98 SUBMITTED | | | | | | A) INDICATES THAT ONLY 10 TESTS WERE PERFORMED. | | | ACCORDING TO SEC. 8 OF TAS 105 NEED TO PROVIDE | | | ADDITIONAL TESTS FORAREAS LARGER THAN 100 SQUARES. | | | SEE SEC. 8. | | | | | | B) ENGINEER TO PROVIDE ALL INFORMATION IN THE REPORT | | | AS REQUIRED BUY SEC. 10 OF TAS 105. | | | | | | C) ENGINEER TO PROVIDE THE ENGINEERING FIRM | | | CERTIFICATE OF AUTHORIZATION NUMBER ON EACH SHEET AS | | | REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE | | | CODE. | | | | | | D) ENGINEER TO SIGN, AND DATE ALL SHEETS AS REQUIRED | | | BY CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF | | | FLORIDA ADMINISTRATIVE CODE.ONLY THE SEAL WAS | | | IMPRESSED IN ALL SHEETS, BUT WITHOUTSIGNATURE AND | | | DATE. | | | | | | 2- SKYLIGHT PRODUCT APPROVAL SUBMITTED DOESN'TMEET | | | THE DESIGN PRESSURES CALCULATED BY THE ENGINEER AT | | | PERIMETER AREA.NEED TO PROVIDE PRODUCT APPROVAL FOR | | | SKYLIGHT THAT MEETS THE CALCULATED DESIGN PRESSURES. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 | | | |
|