| 2007-11-11 15:02:28 | REVIEW #: 3RD |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. FLOOR PLAN CALLS FOR A TOTAL OF 930 CFM. A FOUR TON |
| | AHU WILL PRODUCE 1600 CFM. WHERE WILL THE OTHER 670 CFM |
| | GO? AN AIR DISTRIBUTION SYSTEM SHALL BE DESIGNED AND |
| | INSTALLED TO SUPPLY THE REQUIRED DISTRIBUTION OF AIR IN |
| | ACCORDANCE WITH FBC,M 603.1. |
| | |
| | 2. THIS COMMENT WAS NOT ADDRESSED. NO OUTSIDE AIR |
| | CALCULATIONS PROVIDED. NO OUTSIDE AIR VENTILATION SHOWN |
| | ON PLANS. SHOW COMPLIANCE WITH FBC,M 403.3. |
| | |
| | 3. THIS COMMENT WAS PARTIALLY ADDRESSED. CFM OF BATH |
| | EXHAUST FANS STILL NOT SHOWN ON PLANS. SHOW COMPLIANCE |
| | WITH FBC,M 403.3. |
| | |
| | 4. THIS COMMENT WAS NOT ADDRESSED. SHOW COMPLIANCE WITH |
| | FBC,M 602.2.1 |
| | |
| | 5. THIS COMMENT WAS NOT ADEQUATELY ADDRESSED. LOCATION |
| | OF CONDENSATE DISPOSAL NOT SHOWN. A SHUTOFF SWITCH ON A |
| | CONDENSATE PUMP IS NOT A CODE COMPLIANT MEANS OF |
| | AUXILIARY DRAIN PROTECTION. COMPLY WITH ONE OF THE |
| | ALLOWED METHODS AS LISTED IN FBC,M SECTION 307.2.3. |
| | |
| | 6. OK |
| | |
| | 7. NOW ENERGY CALCULATIONS SHOW 4.8 TONS OF AIR AND |
| | MANUAL N SHOWS 5 TONS OF AIR, BUT EQUIPMENT LISTED IS |
| | ONLY 4 TONS. PLEASE COORDINATE ALL DOCUMENTATION AND |
| | EQUIPMENT LISTING. |
| | |
| | 8. OK |
| | |