| 2007-06-24 12:18:15 | |
| | |
| | *** UNSAT 2ND REVIEW*** |
| | |
| | ** PLANS FAILED FOR MANY OF THE SAME ITEMS AS STATED ON |
| | PREVIOUS REVIEW. PLEASE SEE THERE ARE ALSO NEW COMMENTS |
| | BASED ON REVISIONS AND CHANGES MADE TO PLANS. |
| | ** PLANS ORIGINALLY SUBMITTED UNDER PERMIT NUMBER |
| | 05010378 WHICH BECAME *EXPIRED*. |
| | |
| | |
| | 1) NOTE:THIS REMAINS THE SAME NOTE AS THIS |
| | INFORMATION WAS NOT PLACED ON PLANS. |
| | PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED |
| | CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| | 8TH, 2006. |
| | 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS |
| | SUBMITTED |
| | 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED. |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY |
| | INDICATE CODES NEEDED. |
| | |
| | 2) NOTE:PLEASE CORRELATE ELECTRICAL ON PLANS WITH |
| | THAT OF THE PANEL SCHEDULE(S). |
| | PLEASE SEE THERE ARE COMMENTS BELOW WITH RESPECT TO |
| | CIRCUITING WHICH IS STILL NOT CORRECT. |
| | NEC 408.4 |
| | PLEASE CORRELATE AND COORDINATE ALL. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE PANEL |
| | SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE ARE |
| | SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. PLEASE |
| | SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. *SECTION |
| | 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE |
| | IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | "KITCHEN WALL RECEPTACLES,'' "DINING ROOM FLOOR |
| | RECEPTACLE,'' OR "KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY "LIGHTS'' OR "OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION. |
| | |
| | 3) NOTE: PLEASE SEE THIS IS THE SAME NOTE AS PREVIOUS |
| | REVIEW. PLEASE SEE SEVERAL EMERGENCY LIGHTS AND EXIT |
| | LIGHTS ARE STILL BEING SHOWN ON DEDICATED CIRCUITS |
| | WHICH ARE ONLY PERMITTED UNDER CERTAIN CONDITIONS, |
| | BASED ON PLANS THE EXCEPTIONS AS STATED IN THE NEC DOES |
| | NOT APPLY AND THESE FIXTURES ARE REQUIRED TO BE |
| | CIRCUITED TO THE LOCAL LIGHTING CIRCUIT IN ANY ONE |
| | AREA. PLEASE SEE THE NOTE WITH RESPECT TO LOADS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 700.12F FOR EMERGENCY AND EXIT LIGHTS. |
| | THIS COMMENT WAS MADE ON ALL OTHER REVIEWS UNDER |
| | PREVIOUS PERMIT APPLICATION; HOWEVER NO CHANGES TO |
| | PLANS OR CIRCUITING HAVE BEEN MADE. PLEASE SEE OTHER |
| | AREA ON PLANS WHICH DO NOT SHOW CIRCUITS FOR THESE, |
| | NOTE TO CIRCUIT TO PANEL HOWEVER THESE SHALL BE |
| | CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT. |
| | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | 4) NOTE:PLEASE KNOW THAT COMPLETE LOAD CALCULATIONS |
| | FOR THE PROPOSED SERVICE AND PANELS AS PREVIOUSLY |
| | REQUESTED HAS NOT BEEN SUBMITTED. |
| | PLEASE SEE TWO SEPARATE LOAD CALCULATIONS SHOWN FOR |
| | SAME PANEL? |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SHOW LOAD CALCULATIONS, PLEASE SHOW PER, 220.12, |
| | 220.14, 220.42, 220.44 ETC. |
| | PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER |
| | 215.3, AND 230.42 |
| | PLEASE SEE LOAD CALCULATIONS SUBMITTED DO NOT ALL |
| | CORRELATE WITH THE LOADS SHOWN ON PANELS. PLEASE SEE |
| | SUB PANEL *C*. |
| | PLEASE SHOW LOAD CALCULATIONS FOR SERVICE AS REQUESTED |
| | ON PREVIOUS REVIEWS UNDER OLD EXPIRED PERMIT. PLEASE |
| | SEE ITEMS ON LOAD CALCULATIONS WHICH ARE NOT ON PANEL |
| | SCHEDULE(S). (SIGN CIRCUIT) |
| | |
| | 5) NOTE: PLEASE SEE ONCE AGAIN THE SERVICE RISER HAS |
| | BEEN REVISED AND IS STILL NOT CODE COMPLIANT. PLEASE |
| | SEE NOTES ON E-1 WHICH STATES THIS NEW SERVICE IS A MLO |
| | PANEL WHEREAS THE RISER INDICATES THIS AS A METER/MAIN |
| | COMBO? 230.70, 230.71 (MAIN REQUIRED). PLEASE SEE THE |
| | RISER SHOWS AND NOTES THIS SERVICE AS NEW YET THE RISER |
| | ALSO CONTAINS NOTES FOR EXISTING? PLEASE SEE THE |
| | FEEDERS FOR THE NEW 200AMP PANEL ARE NOT CODE COMPLIANT |
| | PER 310.16 |
| | PLEASE SEE THE RISER WHICH SHOWS TWO MAIN DISCONNECTS: |
| | ONE 200AMPS AND THE OTHER 150AMPS BOTH FEEDING A SINGLE |
| | CONDUIT WITH 2/0 FEEDERS TO A GUTTER WHICH TAPS TO |
| | 125AMP PANEL AND A 150AMP PANEL. THIS ENTIRE SCENARIO |
| | IS NOT CODE COMPLIANT FROM THE FEEDERS, THE TAPS, TO |
| | TERMINATION IN OPC, THE SINGLE CONDUIT WITH TWO |
| | BREAKERS SHOWN FEEDING ONE? ETC ETC. PLEASE SEE 215.5, |
| | 310.16, 240.4, 408, 240.21 ETC. THERE ARE TOO MANY CODE |
| | SECTIONS TO BE REFERENCED. |
| | PLEASE SUBMIT A CODE COMPLIANT RISER. |
| | PLEASE SUBMIT THE PANEL SCHEDULES WHICH INDICATE THE |
| | OCP FEEDING TO SUB PANELS. |
| | PLEASE SEE THE 2005 NEC AND KNOW IF ANY OF THESE |
| | CONDITIONS EXIST AT THIS LOCATION AS SHOWN ON PLANS, |
| | THE ENTIRE ELECTRICAL SERVICE WILL BE REQUIRED TO |
| | BROUGHT UP TO CODE. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE A COMPLETELY NEW RISER DIAGRAM HAS NOW BEEN |
| | SUBMITTED AND IS MISSING INFORMATION NEEDED FOR CODE |
| | COMPLIANCE AND FOR REVIEW. |
| | PLEASE SEE THE NEXT SEVERAL ITEMS ARE BEING STATED IN |
| | THIS ONE COMMENT. |
| | A) PLEASE SEE MISSING AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT AND MAINS. |
| | B) PLEASE SHOW LOCATIONS OF ALL SERVICE EQUIPMENT ON |
| | PLANS. |
| | C) PLEASE CORRELATE PLANS AND RISER AND PANELS. PLEASE |
| | SEE PLANS SHOWS 150A PANEL AS EXISTING, PANEL SCHEDULE |
| | FOR *C* SHOWS 150AMP AND 125AMP. PLEASE SEE LOAD ON |
| | THIS PANEL DOES NOT CORRELATE WITH LOAD CALCULATIONS. |
| | PLEASE SEE PANEL *B* WHICH SHOWS DIFFERENT FEEDERS, |
| | DIFFERENT OVER CURRENT PROTECTION ETC. |
| | D) PLEASE SEE SERVICE ENTRANCE CONDUCTORS ARE NOT RATED |
| | FOR SERVICE. |
| | ETC. |
| | 215.5, 310.16, 408.4, 240.4, 110.9, 240.24, 408.7 ETC |
| | PLEASE SEE 2005 NEC. |
| | |
| | 6) NOTE:PLEASE SEE COMPLIANCE WITH CHAPTER 13 HAS NOT |
| | BEEN MET. |
| | PLEASE SEE NO DESIGN CHANGES OR CONSIDERATION WAS GIVEN |
| | TO PREVIOUS NOTES WITH RESPECT TO LIGHTING CONTROLS |
| | REQUIRED. |
| | PLEASE SEE NO INFORMATION OR RESPONSE TO THESE COMMENT |
| | TO PROVIDE INFORMATION FOR REVIEW WAS IN PACKAGE SO THE |
| | COMMENTS REMAIN. |
| | PLEASE SEE NO TIMED SCHEDULING SYSTEM IS SHOWN IF IN |
| | DESIGN, OTHER MEANS OF LIGHTING CONTROLS MAY BE SUED. |
| | PLEASE SEE NO AUTOMATED DEVICES ARE SHOWN. |
| | PLEASE SEE NO OVER RIDE TIMES ARE SHOWN. |
| | PLEASE SEE NO DEVICE LOCATIONS WERE SHOWN. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED FOR |
| | METHOD OF CONTROLS IS NOT CORRECT. |
| | PLEASE SEE NO OWNER AGENT WAS SIGNED ON SHEETS AS |
| | REQUIRED. |
| | PLEASE SEE THE FIXTURE LEGEND IS NOT COMPLETE WITH ALL |
| | INFORMATION FOR FIXTURES FOR COORDINATION REVIEW WITH |
| | THE SUBMITTED ENERGY CALCULATIONS. |
| | PLEASE SEE NOTE WITH RESPECT TO THE ENGINEER AS SHOWN |
| | CERTIFYING THE ENERGY CALCULATIONS. |
| | PLEASE SEE NO SEPARATE SPACE CONTROLS ARE SHOWN. PLEASE |
| | SEE NOT RESPONSE LETTER WAS SUBMITTED OR INFORMATION |
| | FOR THIS. |
| | PLEASE SEE COMPLIANCE WITH THE 2004 FBC CHAPTER 13 FOR |
| | CONTROL OF LIGHTING PER 13-415.1ABC.1.1, .1.2 AND |
| | .1.3. |
| | PLEASE SEE13-415.1.AB.1.1, 13-415.2 FOR LIGHTING |
| | PERFORMANCE CALCULATIONS ALONG WITH ENERGY |
| | CALCULATIONS. PLEASE BE SURE TO HAVE THE DESIGNER OF |
| | RECORD SIGN, DATE AND SEAL THESE AS REQUIRED PER |
| | 13-103.1.1.1 |
| | |
| | 7) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS WHICH |
| | INDICATE LOADS WHICH EXCEED THE RATING OF THE BREAKERS |
| | AS SHOWN. 240 |
| | |
| | ** PREVIOUS REVIEW NOTES* |
| | PLEASE CORRELATE ALL LOADS, CONDUCTOR SIZES AND OVER |
| | CURRENT PROTECTION DEVICES ON PANEL SCHEDULES. PLEASE |
| | SEE THERE ARE TOO NUMEROUS TO DETAIL EACH,; HOWEVER SEE |
| | LOADS OF 3.5KW ON 1-POLE 20A BREAKERS, SEE 1-POLE 45AMP |
| | BREAKERS, SEE #8 AWG ON 20AMP BREAKERS, SEE 30AMP |
| | BREAKERS ON #12 AWG, 4-POLE BREAKER,ETC ETC. 240.4, |
| | 310.16 ETC. |
| | SEE 2005 NEC. |
| | |
| | |
| | 8) NOTE: PLEASE SEE THE SIGNATURE AS SHOWN ON ENERGY |
| | CALCULATIONS DOES NOT APPEAR TO BE THE SAME AS THE |
| | SIGNATURE ON FILE FOR THIS DESIGNER OF RECORD. FS |
| | 471.025/ FAC 61G15-23.002 |
| | PLEASE SUBMIT A SIGNED, DATED, SEALED, AND NOTARIZED |
| | LETTER FOR LEGAL SIGNATURE VERIFICATION. |
| | PLEASE BE SURE THE NOTARY PLACES INFORMATION ON LETTER |
| | WHICH IS REQUIRED UNDER FS 117.05 |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | PLEASE KNOW THAT DUE TO THE EXTENT OF COMMENTS AND |
| | NATURE OF COMMENT,FOR ELECTRICALREVIEW AND FOR THAT |
| | OF OTHER REQUIREMENTS UNDER FLORIDA STATUTES AND |
| | FLORIDA ADMINISTRATIVE CODE, ONE SET OF PLANS SUBMITTED |
| | ARE BEING RETAINED BY THIS OFFICE. |
| | |
| | 10) NOTE: PLEASE SEE TITLE BLOCK APPEARS TO SHOW |
| | COMPANY/FIRM AND NOT ONLY THE ARCHITECT AS AN |
| | INDIVIDUAL. PLEASE PROVIDE CERTIFICATE OF AUTHORIZATION |
| | NUMBER AS APPLICABLE UNDER FS 481.219, FA C61G1-16.004 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |