| 2007-02-25 13:33:51 | *** UNSAT *** |
| | |
| | ** PLANS ORIGINALLY SUBMITTED UNDER PERMIT NUMBER |
| | 05010378 WHICH BECAME *EXPIRED*. |
| | |
| | **PLEASE SEE MANY OF THE NOTES ARE THE SAME AS STATED |
| | IN ORIGINAL REVIEWS AND NUMEROUS NEW COMMENTS DUE TO |
| | CHANGES MADE TO PLANS WHICH WERE NOT ON PREVIOUS |
| | REVIEWED PLANS AND NOTES FOR NEW CODE CHANGES. |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST |
| | ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER |
| | 8TH, 2006. |
| | 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS |
| | SUBMITTED |
| | 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED. |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE THERE ARE SECTIONS OF CODES REFERENCED |
| | FROM THE 2002 NEC. |
| | |
| | 2) NOTE: PLEASE SEE THERE ARE NUMEROUS NOTES ON PLANS |
| | WHICH REFERENCE ITEMS TO THIS BEING A RESIDENTIAL |
| | DWELLING? PLEASE ADJUST ALL NOTES ACCORDINGLY. THIS |
| | SCOPE OF WORK IS NOT FOR A RESIDENTIAL DWELLING. |
| | |
| | 3) NOTE:PLEASE SHOW ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH PANEL SCHEDULE(S). |
| | PLEASE SEE THERE ARE A FEW ITEMS ON PLANS WHICH STILL |
| | DO NOT SHOW THE CIRCUITING. |
| | PLEASE SEE ALL CIRCUITS WHICH REFLECT TO A PANEL AND |
| | CIRCUITS WHICH ARE NOT PART OF THE SUBMITTED PANEL |
| | SCHEDULES SUBMITTED. |
| | PLEASE ALSO SEE WATER FOUNTAIN HAS BEEN ADDED TO PLANS; |
| | HOWEVER PLANS DO NOT INDICATE ANY ELECTRICAL |
| | RECEPTACLES FOR THIS UNIT. |
| | PLEASE CORRELATE AND COORDINATE ALL. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE |
| | PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE |
| | ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. |
| | PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | "KITCHEN WALL RECEPTACLES,'' "DINING ROOM FLOOR |
| | RECEPTACLE,'' OR "KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY "LIGHTS'' OR "OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION. |
| | |
| | 5) PLEASE SEE 700.12E FOR EMERGENCY AND EXIT LIGHTS. |
| | THIS COMMENT WAS MADE ON ALL OTHER REVIEWS UNDER |
| | PREVIOUS PERMIT APPLICATION; HOWEVER NO CHANGES TO |
| | PLANS OR CIRCUITING HAVE BEEN MADE. PLEASE SEE OTHER |
| | AREA ON PLANS WHICH DO NOT SHOW CIRCUITS FOR THESE, |
| | NOTE TO CIRCUIT TO PANEL HOWEVER THESE SHALL BE |
| | CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT. |
| | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE |
| | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | 6) NOTE: PLEASE SHOW LOAD CALCULATIONS, PLEASE SHOW |
| | PER, 220.12, 220.14, 220.42, 220.44 ETC. |
| | PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER |
| | 215.3, AND 230.42 |
| | PLEASE SEE LOAD CALCULATIONS SUBMITTED DO NOT ALL |
| | CORRELATE WITH THE LOADS SHOWN ON PANELS. PLEASE SEE |
| | SUB PANEL *C*. |
| | PLEASE SHOW LOAD CALCULATIONS FOR SERVICE AS REQUESTED |
| | ON PREVIOUS REVIEWS UNDER OLD EXPIRED PERMIT. PLEASE |
| | SEE ITEMS ON LOAD CALCULATIONS WHICH ARE NOT ON PANEL |
| | SCHEDULE(S). (SIGN CIRCUIT) |
| | |
| | 7) NOTE: PLEASE SEE A COMPLETELY NEW RISER DIAGRAM HAS |
| | NOW BEEN SUBMITTED AND IS MISSING INFORMATION NEEDED |
| | FOR CODE COMPLIANCE AND FOR REVIEW. |
| | PLEASE SEE THE NEXT SEVERAL ITEMS ARE BEING STATED IN |
| | THIS ONE COMMENT. |
| | A) PLEASE SEE MISSING AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT AND MAINS. |
| | B) PLEASE SHOW LOCATIONS OF ALL SERVICE EQUIPMENT ON |
| | PLANS. |
| | C) PLEASE CORRELATE PLANS AND RISER AND PANELS. PLEASE |
| | SEE PLANS SHOWS 150A PANEL AS EXISTING, PANEL SCHEDULE |
| | FOR *C* SHOWS 150AMP AND 125AMP. PLEASE SEE LOAD ON |
| | THIS PANEL DOES NOT CORRELATE WITH LOAD CALCULATIONS. |
| | PLEASE SEE PANEL *B* WHICH SHOWS DIFFERENT FEEDERS, |
| | DIFFERENT OVER CURRENT PROTECTION ETC. |
| | D) PLEASE SEE SERVICE ENTRANCE CONDUCTORS ARE NOT RATED |
| | FOR SERVICE. |
| | ETC. |
| | 215.5, 310.16, 408.4, 240.4, 110.9, 240.24, 408.7 ETC |
| | PLEASE SEE 2005 NEC. |
| | |
| | 8) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| | CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE SUBMIT ENERGY CALCULATIONS PER THE 2004 FBC W/ |
| | 2006 REVISION. PLEASE SEE ENERGY CALCULATIONS SUBMITTED |
| | ARE FROM THE 2001 FBC. |
| | PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE |
| | CALCULATIONS ALONG WITH ENERGY CALCULATIONS. PLEASE BE |
| | SURE TO HAVE THE DESIGNER OF RECORD SIGN, DATE AND SEAL |
| | THESE AS REQUIRED PER 13-103.1.1.1 |
| | |
| | 9) NOTE: PLEASE SEE FLORIDA STATUES 481.221 WHICH |
| | REQUIRES TO THE ARCHITECT TO ALSO DATE PLANS WHEN |
| | SIGNING AND SEALING SAID PLANS. |
| | |
| | 10) NOTE: PLEASE SEE PLANS SUBMITTED ARE IN FACT |
| | COLORED PHOTO-COPIES OF PLANS STAMPED PREVIOUSLY BY THE |
| | CITY ZONING REVIEWER AND PALM BEACH COUNTY FOR IMPACT |
| | FEES. PLEASE KNOW THAT THESE SHALL BE ORIGINAL AND MAY |
| | NOT MAKE CHANGES TO PLANS AND COLOR PHOTO-COPY PLANS. |
| | PLANS WILL BE REQUIRED TO GO BACK TO HISTORIC, ZONING, |
| | AND PALM BEACH COUNTY AS PERMIT APPLICATION IS NOW |
| | UNDER NEW PALM BEACH COUNTY IMPACT FEE SCHEDULE AS OF |
| | JAN 1ST, 2006. |
| | |
| | 11) NOTE: PLEASE SEE PLANS WHICH STILL STATE *CORAL KEY |
| | DESIGN*. PLEASE KNOW AS PER FS481.229, A DESIGNER, |
| | DRAFTING, CADD DESIGN COMPANY MAY NOT DESIGN PLANS |
| | FORCOMMERICAL/ PUBLIC USE OF THIS NATURE. THIS HAS BEEN |
| | CONFIRMED WITH THE STATE OF FLORIDA LEGAL COUNSEL TO |
| | THE BOARD OF ARCHITECTS AND THIS COMMENT WAS MADE ON |
| | PREVIOUS REVIEWS UNDER THE EXOIRED PERMIT. |
| | FURTHER CONTACT MAY BE DONE WITH STATE PROSECUTOR |
| | MR.DAVID MINACCI, OR STATE INVESTIGATOR MR. LES SMITH. |
| | |
| | 12) NOTE: PLEASE CORRELATE ALL LOADS, CONDUCTOR SIZES |
| | AND OVER CURRENT PROTECTION DEVICES ON PANEL |
| | SCHEDULES. |
| | PLEASE SEE THERE ARE TOO NUMEROUS TO DETAIL EACH,; |
| | HOWEVER SEE LOADS OF 3.5KW ON 1-POLE 20A BREAKERS, SEE |
| | 1-POLE 45AMP BREAKERS, SEE #8 AWG ON 20AMP BREAKERS, |
| | SEE 30AMP BREAKERS ON #12 AWG, 4-POLE BREAKER,ETC |
| | ETC. |
| | 240.4, 310.16 ETC. |
| | SEE 2005 NEC. |
| | |
| | 13) NOTE: PLEASE SEE MISSING A/C UNITS AND THERE |
| | REQUIRED DISCONNECTING MEANS PER 440.11. PLEASE SEE |
| | MISSING CU DISCONNECT, PLEASE SEE MISSING AHU |
| | DISCONNECT ETC. PLEASE SEE SOME SHOWN WITH A RECEPTACLE |
| | FOR UNIT TO PLUG-IN WHICH IS PROHIBITED. |
| | 422.30, 422.31, 440.11 ETC. |
| | |
| | 14) NOTE: PLEASE SEE AHU'S WITH OVER CURRENT PROTECTION |
| | WHICH IS TOO HIGH FOR THE 5KW LOAD SHOWN. AHU'S #1 AND |
| | #2. |
| | 240.4, 310.16, AND FBC 106.1.2, 106.3.5.1.2 FOR |
| | COORDINATION. |
| | |
| | |
| | 15) NOTE: PLEASE KNOW THAT DUE TO THE EXTENT OF |
| | COMMENTS AND NATURE OF COMMENT,FOR ELECTRICALREVIEW |
| | AND FOR THAT OF OTHER REQUIREMENTS UNDER FLORIDA |
| | STATUTES AND FLORIDA ADMINISTRATIVE CODE, ONE SET OF |
| | PLANS SUBMITTED ARE BEING RETAINED BY THIS OFFICE. |
| | |
| | 16) NOTE: PLEASE SEE THAT THE NEWLARGER ADA BATHROOM |
| | SHALL CONTAIN A BATTERY BACK UP LIGHTING FIXTURE FO |
| | SOME TYPE. LS 101 7.8, 7.9. PLEASE CIRCUIT PER 700.12 |
| | FO TEH NEC. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |