| Plan Review Notes For Permit 07020122 |
| Permit Number |
07020122 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-03-06 15:02:37 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL | | | SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO | | | BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5 | | | NEC 2005. | | | | | | 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND | | | 106.3.5.4(8) FBC. | | | | | | 3} THE AIR HANDLER LOCATED IN THE CLOSET, HAVING | | | OVERCURRENT PROTECTION BUILT IN, IS IN VIOLATION OF | | | 240.24(B), 2005NEC. | | | | | | 4} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | | 440.14,RECEPTACLE PER 210.63, FOR THE CONDENSING | | | UNIT. | | | | | | 5} A SMOKE ALARM MUST BE LOCATED OUTSIDE THE "NEW | | | FLORIDA ROOM" , A SLEEPING AREA BY DEFINITION.THE ONE | | | SHOWN IN THE HALL IS NOT "OUTSIDE, AS IT IS IN THE SAME | | | AREA WITH THE DOOR SHUT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|