| Plan Review Notes For Permit 07020113 |
| Permit Number |
07020113 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-13 08:13:57 | *** DENIED *** | | | 1) THE PLANS NEED TO BE SIGNED AND SEALED BY THE | | | ARCHITECT AS THEIR NAME APPEARS IN THE TITLE BLOCK, PER | | | FAC 61G1-16.003. | | | | | | 2) THE PLANS NEED THE JOB ADDRESS IN THE TITLE BLOCK, | | | PER FAC 61G1-16.004. | | | | | | 3) THE 8" RETURN AIR TRANSFER DUCT TO BEDROOM #3 NEEDS | | | TO BE 9", SEE 2004 FBC/R M1602.4 (A). | | | | | | 4) THE 10" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE | | | NEEDS TO BE 14", SEE 2004 FBC/R M1602.4 (A) AND (C) | | | EXCEPT. | | | | | | *** 2004 FBC/R M1602.4 BALANCED RETURN AIR MAY BE | | | ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | | ACHIEVE PROPER RETURN AIR BALANCE. | | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|