Plan Review Notes
Plan Review Notes For Permit 07020113
Permit Number 07020113
Review Stop M
Sequence Number 1
Notes
Date Text
2007-02-13 08:13:57*** DENIED ***
 1) THE PLANS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT AS THEIR NAME APPEARS IN THE TITLE BLOCK, PER
 FAC 61G1-16.003.
  
 2) THE PLANS NEED THE JOB ADDRESS IN THE TITLE BLOCK,
 PER FAC 61G1-16.004.
  
 3) THE 8" RETURN AIR TRANSFER DUCT TO BEDROOM #3 NEEDS
 TO BE 9", SEE 2004 FBC/R M1602.4 (A).
  
 4) THE 10" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE
 NEEDS TO BE 14", SEE 2004 FBC/R M1602.4 (A) AND (C)
 EXCEPT.
  
 *** 2004 FBC/R M1602.4 BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved