| 2007-02-06 17:02:22 | | | | | | | | | | NONCOMPLIANT | | | | | | THE PLANS SUBMITTED INDICATE THE COMPLETE WIRING OF | | | THIS RESIDENCE, IF THAT IS NOT THE INTENT, ONLY SUBMIT | | | PLANS FOR THE ACTUAL DESCRIPTION OF WORK TO BE DONE. | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1}INDICATE THE SERVICE EQUIPMENT LOCATION. THE PLAN | | | SHOWS THE SERVICE IN TWO LOCATIONS. | | | | | | 2} PUT THE ADDRESS OF THE RESIDENCE OR A LEGAL | | | DISCRIPTION BY WHICH IT CAN BE IDENTIFIED, ON THE | | | PLAN. | | | | | | 3} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON | | | THE PLANS, MUST SIGN AND SEAL THE PLAN PER | | | 481.221(1)(B)FS. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|