Plan Review Notes
Plan Review Notes For Permit 07020105
Permit Number 07020105
Review Stop B
Sequence Number 2
Notes
Date Text
2007-03-14 11:31:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)THE PLAN STATES THAT THE DAMAGE IS 6' NORTH FROM
 COMMON LINE OF BUILDINGS, ENGINEER'S NOTES 2, SHEET 1.
 WERE FIRE RATED WALLS AFFECTED?FROM THE WRITTEN
 DESCRIPTION IT DOES NOT APPEAR TO BE AT THE WALL
 SEPARATING THE BUILDINGS, BUT THE ELEVATION ON SHEET 1
 SHOWS THE DAMAGE AT A CORNER/WALL.THE EXISTING FLOOR
 PLAN SHOWS THIS CORNER AS A TENANT SEPARATION.IF A
 FIRE RATED WALL WAS AFFECTED, PROVIDE A DETAIL FOR
 REPAIR SHOWING FIRE RATING REQUIREMENT (TENANT OR
 OCCUPANCY SEPARATION OR OTHER FIRE RATING REQUIRED BY
 FBC CHAPTER 5 OR FBC CHAPTER 6) AND COMPLIANCE WITH
 EITHER A TESTED ASSEMBLY OR CALCULATED FIRE RESISTANCE,
 FBC CHAPTER 9.
  
 2.)NEW SHEETS WERE SUBMITTED.IT IS NOT CLEAR WHY AN
 EXISTING BUILDING PLANS WERE SUBMITTED, ESPECIALLY AS
 ONE OF THE SHEETS IS ILLEGIBLE.PLEASE SHOW LOCATION
 OF THE REPAIR ON THESE SHEETS, ALTHOUGH IT IS NOT CLEAR
 WHY ELECTRIC SHEETS ARE SUBMITTED.
  
 3.)THE PROJECT DESCRIPTON STATES THAT THE WINDOWS
 WILL BE REPLACED.NO PRODUCT APPROVALS SUBMITTED.ANY
 PRODUCT APPROVALS NOT REVIEWED PRIOR TO PERMIT ISSUANCE
 WILL REQUIRE SEPARATE PERMITS.PRODUCT APPROVALS ARE
 TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL,FBC*106.3.3.