Plan Review Notes
Plan Review Notes For Permit 07020102
Permit Number 07020102
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-08 09:11:44** UNSAT **
  
 1) NOTE: PLEASE SEE THE PANEL SCHEDULE HAS NOW BEEN
 SUBMITTED THE NEW CIRCUITS AND OTHERS APPEAR TO BE
 EXISTING HOWEVER REVISED LOAD CALCULATIONS WAS NOT DONE
 FOR EXISTING LOADS AND NEW LOADS BEING ADDED. PLEASE
 SEE THE .25VA PER SQFT BEING SHOWN FOR COMPLETE NEW
 LOADS IS NOT CORRECT AT THIS TIME.
 PLEASE SEE 220.12 AS THIS LOAD IS ONLY FOR THE LIGHTING
 LOADS WHEN NO SPECIFIC LOADS ARE KNOWN.
 PLEASE SEE THE LOADS WHICH ARE TO BE FIGURED FOR ANY
 RECEPTACLES LOADS ARE TO BE BASED ON 220.14I. PLEASE
 SEE THIS IS A MINIMUM OF 180VA FOR EACH KNOWN
 DEVICE/YOKE.
 PLEASE SEE THE PLANS DO CONTAIN THE SPECIFIC NUMBER OF
 DEVICES. PLEASE ALSO SEE THE SPECIFIC LOADS SUCH AS THE
 GARAGE DOOR WHICH IS A MOTOR LOAD MAY NOT FIGURED INTO
 THE .25VA FOR LIGHTS.
 PLEASE SEE PLANS NOW ALSO CONTAIN A NEW EXHAUST FAN
 WHICH ALSO CAN NOT BE FIGURED INTO THE GENERAL LIGHT
 LOADS.
  
 PLEASE SEE 220, 430 OF THE NEC AND PLEASE ADJUST AND
 REVISE.
  
 2) NOTE: PLEASE SEE BOTH SETS OF THE ARCHITECTURAL
 SHEETS ARE SIGNED AND DATED, HOWEVER DO NOT CONTAIN A
 RAISED SEAL ON ANY SHEET IN EITHER SET.
 FS 481.221
  
 3) NOTE: PLEASE SEE THE LOCATION OF THE NEW EXHAUST FAN
 IS IN QUESTION AS IT SEEM TO BE ON THE WALL WHICH ABUTS
 UP TO THE SOUTH WALL WHICH IS ALSO ADJACENT TO THE
 OTHER WALL OF THE BUILDING WHICH IS ON ANOTHER
 PROPERTY?
 PLEASE SEE THIS ISSUE MAY COME UP AS EXHAUSTING OVER
 THE PROPERTY LINE AND AS SHOWN IS INTO THE BUILDING
 NEXT DOOR.
 ** PLEASE SEE NOTES FROM MECHANCIAL AND BUILDING
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]