| 2007-04-08 09:11:44 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THE PANEL SCHEDULE HAS NOW BEEN |
| | SUBMITTED THE NEW CIRCUITS AND OTHERS APPEAR TO BE |
| | EXISTING HOWEVER REVISED LOAD CALCULATIONS WAS NOT DONE |
| | FOR EXISTING LOADS AND NEW LOADS BEING ADDED. PLEASE |
| | SEE THE .25VA PER SQFT BEING SHOWN FOR COMPLETE NEW |
| | LOADS IS NOT CORRECT AT THIS TIME. |
| | PLEASE SEE 220.12 AS THIS LOAD IS ONLY FOR THE LIGHTING |
| | LOADS WHEN NO SPECIFIC LOADS ARE KNOWN. |
| | PLEASE SEE THE LOADS WHICH ARE TO BE FIGURED FOR ANY |
| | RECEPTACLES LOADS ARE TO BE BASED ON 220.14I. PLEASE |
| | SEE THIS IS A MINIMUM OF 180VA FOR EACH KNOWN |
| | DEVICE/YOKE. |
| | PLEASE SEE THE PLANS DO CONTAIN THE SPECIFIC NUMBER OF |
| | DEVICES. PLEASE ALSO SEE THE SPECIFIC LOADS SUCH AS THE |
| | GARAGE DOOR WHICH IS A MOTOR LOAD MAY NOT FIGURED INTO |
| | THE .25VA FOR LIGHTS. |
| | PLEASE SEE PLANS NOW ALSO CONTAIN A NEW EXHAUST FAN |
| | WHICH ALSO CAN NOT BE FIGURED INTO THE GENERAL LIGHT |
| | LOADS. |
| | |
| | PLEASE SEE 220, 430 OF THE NEC AND PLEASE ADJUST AND |
| | REVISE. |
| | |
| | 2) NOTE: PLEASE SEE BOTH SETS OF THE ARCHITECTURAL |
| | SHEETS ARE SIGNED AND DATED, HOWEVER DO NOT CONTAIN A |
| | RAISED SEAL ON ANY SHEET IN EITHER SET. |
| | FS 481.221 |
| | |
| | 3) NOTE: PLEASE SEE THE LOCATION OF THE NEW EXHAUST FAN |
| | IS IN QUESTION AS IT SEEM TO BE ON THE WALL WHICH ABUTS |
| | UP TO THE SOUTH WALL WHICH IS ALSO ADJACENT TO THE |
| | OTHER WALL OF THE BUILDING WHICH IS ON ANOTHER |
| | PROPERTY? |
| | PLEASE SEE THIS ISSUE MAY COME UP AS EXHAUSTING OVER |
| | THE PROPERTY LINE AND AS SHOWN IS INTO THE BUILDING |
| | NEXT DOOR. |
| | ** PLEASE SEE NOTES FROM MECHANCIAL AND BUILDING |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |