| Date |
Text |
| 2007-05-02 14:34:09 | *** DENIED *** |
| | 1) THE ARCHITECT WHO'S INFORMATION IS IN THE TITLE |
| | BLOCK MUST SEAL THE PLANS. SEE FAC 61G1-16.003 SEAL, |
| | SIGNATURE AND DATE SHALL BE AFFIXED. |
| | |
| | 2) PLANS PAGE 2 SHOW AN EXHAUST FAN ON THE SOUTH WALL |
| | NEXT TO ANOTHER BUILDING ON A ZERO LOT LINE, SEE 2004 |
| | FBC/M 502.7.3.6. PLEASE CORRECT. |
| | |
| | ** 2004 FBC/M 502.7.3.6 TERMINATION POINT. |
| | THE TERMINATION POINT FOR EXHAUST DUCTS DISCHARGING TO |
| | THE ATMOSPHERE SHALL BE LOCATED WITH THE FOLLOWING |
| | MINIMUM DISTANCES. |
| | 1.FOR DUCTS CONVEYING EXPLOSIVE OR FLAMMABLE |
| | VAPORS, FUMES OR DUSTS: 30 FEET (9144 MM) FROM THE |
| | PROPERTY LINE; 10 FEET (3048 MM) FROM OPENINGS INTO THE |
| | BUILDING; 6 FEET (1829 MM) FROM EXTERIOR WALLS AND |
| | ROOFS; 30 FEET (9144 MM) FROM COMBUSTIBLE WALLS AND |
| | OPENINGS INTO THE BUILDING WHICH ARE IN THE DIRECTION |
| | OF THE EXHAUST DISCHARGE; 10 FEET (3048 MM) ABOVE |
| | ADJOINING GRADE. |
| | 2.FOR OTHER PRODUCT-CONVEYING OUTLETS: 10 FEET |
| | (3048 MM) FROM THE PROPERTY LINE; 3 FEET (914 MM) FROM |
| | EXTERIOR WALLS AND ROOFS; 10 FEET (3048 MM) FROM |
| | OPENINGS INTO THE BUILDING; 10 FEET (3048 MM) ABOVE |
| | ADJOINING GRADE. |
| | 3.FOR ENVIRONMENTAL AIR DUCT EXHAUST: 3 FEET (914 |
| | MM) FROM THE PROPERTY LINE; 3 FEET (914 MM) FROM |
| | OPENINGS INTO THE BUILDING. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |