2007-05-02 14:34:09*** DENIED ***
 1) THE ARCHITECT WHO'S INFORMATION IS IN THE TITLE
 BLOCK MUST SEAL THE PLANS. SEE FAC 61G1-16.003 SEAL,
 SIGNATURE AND DATE SHALL BE AFFIXED.
  
 2) PLANS PAGE 2 SHOW AN EXHAUST FAN ON THE SOUTH WALL
 NEXT TO ANOTHER BUILDING ON A ZERO LOT LINE, SEE 2004
 FBC/M 502.7.3.6. PLEASE CORRECT.
  
 ** 2004 FBC/M 502.7.3.6 TERMINATION POINT.
 THE TERMINATION POINT FOR EXHAUST DUCTS DISCHARGING TO
 THE ATMOSPHERE SHALL BE LOCATED WITH THE FOLLOWING
 MINIMUM DISTANCES.
 1.FOR DUCTS CONVEYING EXPLOSIVE OR FLAMMABLE
 VAPORS, FUMES OR DUSTS: 30 FEET (9144 MM) FROM THE
 PROPERTY LINE; 10 FEET (3048 MM) FROM OPENINGS INTO THE
 BUILDING; 6 FEET (1829 MM) FROM EXTERIOR WALLS AND
 ROOFS; 30 FEET (9144 MM) FROM COMBUSTIBLE WALLS AND
 OPENINGS INTO THE BUILDING WHICH ARE IN THE DIRECTION
 OF THE EXHAUST DISCHARGE; 10 FEET (3048 MM) ABOVE
 ADJOINING GRADE.
 2.FOR OTHER PRODUCT-CONVEYING OUTLETS: 10 FEET
 (3048 MM) FROM THE PROPERTY LINE; 3 FEET (914 MM) FROM
 EXTERIOR WALLS AND ROOFS; 10 FEET (3048 MM) FROM
 OPENINGS INTO THE BUILDING; 10 FEET (3048 MM) ABOVE
 ADJOINING GRADE.
 3.FOR ENVIRONMENTAL AIR DUCT EXHAUST: 3 FEET (914
 MM) FROM THE PROPERTY LINE; 3 FEET (914 MM) FROM
 OPENINGS INTO THE BUILDING.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  