2007-03-20 12:44:58*****DENIED*****
  
  
  
 1.NFPA 101- 2003 EDITION SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION. ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE ERECTING AND (OR) INSTALLATION OF THE STORAGE
 ADDITION SHALL NOT INTERFERE OR HINDER EMERGENCY ACCESS
 TO THE PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.INDICATE THE CLASSIFICATION OF CONTENT TO BE STORED
 AS LOW HAZARD, INTERMEDIATE HAZARD, OR HIGH HAZARD
 DEPENDING ON THE CHARACTER OF THE MATERIALS STORED,
 THEIR PACKAGING, AND OTHER FACTORS.
  
 6.PROVIDE THE OCCUPANT LOAD OR MAXIMUM PROBABLE
 POPULATION FOR THIS SPACE UNDER CONSIDERATION.
  
 7.PROVIDE THE INTERIOR WALL AND CEILING
 CLASSIFICATION.PLEASE BE ADVISED THAT CLASS A, CLASS
 B, OR CLASS C SHALL BE REQUIRED FOR STORAGE AREAS AND
 EXIT ENCLOSURES.PLEASE SPECIFY WHICH CLASSIFICATION.
  
 8.WILL THE STRUCTURE HAVE A FIRE SPRINKLER AND (OR)
 FIRE ALARM SYSTEM?
  
 9.ALTHOUGH NOT REQUIRED BY NFPA 101, IT IS
 RECOMMENDED BY WEST PALM BEACH FIRE PREVENTION THAT AT
 LEAST ONE 2A:10BC FIRE EXTINGUISHER BE INSTALLED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW