| 2007-03-20 12:44:58 | *****DENIED***** |
| | |
| | |
| | |
| | 1.NFPA 101- 2003 EDITION SHALL BE REFERENCED. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION. ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.THE ERECTING AND (OR) INSTALLATION OF THE STORAGE |
| | ADDITION SHALL NOT INTERFERE OR HINDER EMERGENCY ACCESS |
| | TO THE PROPERTY OR VICINITY THEREOF (INCLUDING FIRE |
| | LANES). |
| | |
| | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 5.INDICATE THE CLASSIFICATION OF CONTENT TO BE STORED |
| | AS LOW HAZARD, INTERMEDIATE HAZARD, OR HIGH HAZARD |
| | DEPENDING ON THE CHARACTER OF THE MATERIALS STORED, |
| | THEIR PACKAGING, AND OTHER FACTORS. |
| | |
| | 6.PROVIDE THE OCCUPANT LOAD OR MAXIMUM PROBABLE |
| | POPULATION FOR THIS SPACE UNDER CONSIDERATION. |
| | |
| | 7.PROVIDE THE INTERIOR WALL AND CEILING |
| | CLASSIFICATION.PLEASE BE ADVISED THAT CLASS A, CLASS |
| | B, OR CLASS C SHALL BE REQUIRED FOR STORAGE AREAS AND |
| | EXIT ENCLOSURES.PLEASE SPECIFY WHICH CLASSIFICATION. |
| | |
| | 8.WILL THE STRUCTURE HAVE A FIRE SPRINKLER AND (OR) |
| | FIRE ALARM SYSTEM? |
| | |
| | 9.ALTHOUGH NOT REQUIRED BY NFPA 101, IT IS |
| | RECOMMENDED BY WEST PALM BEACH FIRE PREVENTION THAT AT |
| | LEAST ONE 2A:10BC FIRE EXTINGUISHER BE INSTALLED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH COMMENT |
| | WAS ADDRESSED |
| | |
| | |