Plan Review Notes
Plan Review Notes For Permit 07020102
Permit Number 07020102
Review Stop E
Sequence Number 1
Notes
Date Text
2007-02-14 15:18:20**** UNSAT ****
  
 1) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH
 RESPECT TO THE REAR OF BUILDING AND RELATIVE LOCATION
 OF THE PROPERTY LINE AND FEC.
  
 2) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH
 RESPECT TO PALM BEACH COUNTY IMPACT FEES REQUIRED FOR
 ADDITION.
  
 3) NOTE: PLEASE SEE LANDSCAPE PLANS WHICH IS MISSING
 REQUIRED INFORMATION IN TITLE BLOCK(S) PER FAC
 61G1-16.004 AND FLORIDA STATUTES 481.219. PLEASE SEE
 THE MISSING " CERTIFICATE OF AUTHORIZATION* NUMBER. IF
 THERE ARE ANY QUESTIONS ON THIS PLEASE DO NOT HESITATE
 IN CONTACTING THIS OFFICE.
  
 4) NOTE: PLEASE SEE NOTE ON PLANS MENTIONS THE EM/ EXT
 LTS ARE GOING TO BE WIRED AHEAD OF THE NORMAL LIGHTING
 BRANCH CIRCUIT; HOWEVER THE CIRCUITS AS SHOWN ON THE
 PLANS DO NOT CORRELATE WITH THIS. THEY ARE ACTUALLY
 SHOWING TWO SEPARATE CIRCUITS.
 PLEASE SEE 700.12E.
  
 5) NOTE: PLEASE PROVIDE THE UPDATE PANEL SCHEDULE AND
 LOADS BEING INCREASED ON THE EXISTING PANEL WITH THE
 EXISTING LOADS. PLEASE INDICATE THE CONDUCTOR SIZES
 WITH THE OVER CURRENT PROTECTION FOR BREAKERS. 215.5,
 220, 310.16, 240.4,ETC.
 106.3.5.1.2, 106.1.2 ADMIN SECTION OF THE FBC.
  
 6) NOTE: PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE
 STATE OF FLORIDA ADOPTED THE 2006 REVISIONS TO THE 2004
 FBC AND THE 2005 NFPA-70.
 PLEASE KNOW THAT THIS ADDITION AND PLANS ARE REQUIRED
 TO STATE THESE CODES AT A MINIMUM AND SHALL ALSO BE
 DESIGNED UNDER ANY NEW CODES.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]