| 2007-06-05 16:47:39 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- ONLY ONE SET OF PLANS WAS SUBMITTED AND IT WAS NOT |
| | SIGNED AND SEALED BY THE ARCHITECT OF RECORD.NEED TWO |
| | COMPLETE SETS OF DRAWINGS WITH ORIGINAL SEAL AND |
| | SIGNATURE AS REQUIRED BY CHAPTER 481 FLORIDA STATUTES. |
| | |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) HARDIE BOARD SIDING. |
| | |
| | B) SINGLE HUNG WINDOWS WITH DESIGN PRESSURES RATING |
| | OF -90PSF AND +58.7 AS SPECIFIED ON WINDOW SCHEDULE. |
| | |
| | C) ALL STRUCTURAL SIMPSON CONNECTORS SPECIFIED ON |
| | PLANS,DETAILS AND ARCHITECT'S CHECKLIST RESPONSE |
| | LETTER. |
| | |
| | D) STORM SHUTTERS. AND, INDICATE SPECIFIC ANCHOR |
| | TYPE AND SPACING TO BE USED. SEESTORM SHUTTERS |
| | ENGINEERED DRAWINGS AND CIRCLE SPECIFIC ANCHOR. |
| | |
| | E) FLAT ROOF ASSEMBLY. CLEARLY IDENTIFY SPECIFIC |
| | APPROVED ASSEMBLY AND PROVIDE NAIL ENHANCING FOR |
| | PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION #7 |
| | ON PRODUCT APPROVAL AND PROVIDE REQUIRED INFORMATION. |
| | |
| | 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 OF CITY AMENDMENTS TO FBC 2004. |
| | |
| | 5- REVISE ROOF SHEATHING NAILING SPECIFICATIONS. NEED |
| | TO USE MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC. |
| | R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- OWES $101 FOR UPDATED VALUATION AS REQUIRED BY SEC. |
| | 108.3 OF CITY AMENDMENTS TO FBC 2004. |
| | |
| | 7- ARCHITECT TO PROVIDE ORIGINAL SIGNATURE AND SEAL TO |
| | CHECKLIST RESPONSE LETTER AND TO SIGN AND SEAL |
| | CALCULATIONS SUBMITTED AS REQUIRED BY CHAPTER 481 |
| | FLORIDA STATUTE. PROVIDE 2 COPIES. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |