2007-06-05 16:47:39BUILDING REVIEW SECOND CHECKLIST:
 1- ONLY ONE SET OF PLANS WAS SUBMITTED AND IT WAS NOT
 SIGNED AND SEALED BY THE ARCHITECT OF RECORD.NEED TWO
 COMPLETE SETS OF DRAWINGS WITH ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 481 FLORIDA STATUTES.
  
 2-NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) HARDIE BOARD SIDING.
  
 B) SINGLE HUNG WINDOWS WITH DESIGN PRESSURES RATING
 OF -90PSF AND +58.7 AS SPECIFIED ON WINDOW SCHEDULE.
  
 C) ALL STRUCTURAL SIMPSON CONNECTORS SPECIFIED ON
 PLANS,DETAILS AND ARCHITECT'S CHECKLIST RESPONSE
 LETTER.
  
 D) STORM SHUTTERS. AND, INDICATE SPECIFIC ANCHOR
 TYPE AND SPACING TO BE USED. SEESTORM SHUTTERS
 ENGINEERED DRAWINGS AND CIRCLE SPECIFIC ANCHOR.
  
 E) FLAT ROOF ASSEMBLY. CLEARLY IDENTIFY SPECIFIC
 APPROVED ASSEMBLY AND PROVIDE NAIL ENHANCING FOR
 PERIMETER AND CORNER AREAS. SEE GENERAL LIMITATION #7
 ON PRODUCT APPROVAL AND PROVIDE REQUIRED INFORMATION.
  
 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 OF CITY AMENDMENTS TO FBC 2004.
  
 5- REVISE ROOF SHEATHING NAILING SPECIFICATIONS. NEED
 TO USE MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 6- OWES $101 FOR UPDATED VALUATION AS REQUIRED BY SEC.
 108.3 OF CITY AMENDMENTS TO FBC 2004.
  
 7- ARCHITECT TO PROVIDE ORIGINAL SIGNATURE AND SEAL TO
 CHECKLIST RESPONSE LETTER AND TO SIGN AND SEAL
 CALCULATIONS SUBMITTED AS REQUIRED BY CHAPTER 481
 FLORIDA STATUTE. PROVIDE 2 COPIES.
  